6-20 MM2 Motor Manager 2
GE Power Management
6.5 MEMORY MAP 6 COMMUNICATIONS
6
6.5.2 MEMORY MAP TABLE
Table 6–12: MODBUS MEMORY MAP (Sheet 1 of 21)
GROUP MOD-
ICON
REGISTER
ADDRESS DESCRIPTION REGISTE
R VALUE
RANGE
STEP
VALUE
UNITS
AND
SCALE
FOR-
MAT
FACTORY
DEFAULT
VALUE
(CONVERTED)
DEC HEX
Actual Values (Input Registers) Addresses - 0000-0FFF
PRODUCT
ID
30001 0 0000 GE Product Device Code --- --- --- F1 60
30002 1 0001 Hardware Version Code --- --- --- F4 current version
30003 2 0002 Main Software Version Code --- --- --- F1 current version
30004 3 0003 Modification File Number --- --- --- F1 mod. file no.
30005 4 0004 Boot Software Version Code --- --- --- F1 current version
30006 5 0005 Supervisor Processor Version Code --- --- --- F1 current version
30007 6 0006 GE Product Options --- --- --- F111 from order code
30008 7 0007 Serial Number char. 1 and 2 --- --- ASCII F10 char. 1 and 2
30009 8 0008 Serial Number char. 3 and 4 --- --- ASCII F10 char. 1 and 2
30010 9 0009 Serial Number char. 5 and 6 --- --- ASCII F10 char. 1 and 2
30011 10 000A Serial Number char. 7 and 8 --- --- ASCII F10 char. 1 and 2
30012 11 000B Manufacture Month/day --- --- --- F33 manuf. mo./day
30013 12 000C Manufacture year --- --- --- F34 manuf. year
30014 13 000D ...Reserved... ... ... ... ... ...
30015 14 000E Display Processor F/W Version Code F1 current version
30016 15 000F ...Reserved... ... ... ... ... ...
STATUS 30017 16 0010 Switch Input Status --- --- --- F100 N/A
30018 17 0011 LED Status Flags 1 --- --- --- F101 N/A
30019 18 0012 LED Status Flags 2 --- --- --- F102 N/A
30020 19 0013 Operation Status Flags --- --- --- F103 N/A
30021 20 0014 General Alarm Active Status Flags 1 --- --- --- F104 N/A
30022 21 0015 General Alarm Active Status Flags 2 --- --- --- F105 N/A
30023 22 0016 Interlock Alarm Active Status Flags --- --- --- F106 N/A
30024 23 0017 General Alarm Pickup Status Flags 1 --- --- --- F104 N/A
30025 24 0018 General Alarm Pickup Status Flags 2 --- --- --- F105 N/A
30026 25 0019 Interlock Alarm Pickup Status Flags --- --- --- F106 N/A
30027 26 001A Interlock Start Block Status Flags --- --- --- F106 N/A
30028 27 001B Trip Active Status Flags 1 --- --- --- F107 N/A
30029 28 001C Trip Active Status Flags 2 --- --- --- F108 N/A
30030 29 001D Trip Pickup Status Flags 1 --- --- --- F107 N/A
30031 30 001E Trip Pickup Status Flags 2 --- --- --- F108 N/A
30032 31 001F Start Status Flags --- --- --- F109 N/A
Notes: * – Maximum setpoint value and 65535 represent OFF
** – 1/Phase Current Scale Factor x A
*** – 101 represents unlimited
† – Minimum setpoint value represents OFF
~* – 0.1 x A when Hi resolution mode is disabled; 0.01 x A when enabled