CHAPTER 6: ACTUAL VALUES STATUS
T35 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 6-9
6
The AVERAGE MSG RETURN TIME is the time taken for direct output messages to return to the sender in a direct input/output
ring configuration (this value is not applicable for non-ring configurations). This is a rolling average calculated for the last
ten messages. There are two return times for dual-channel communications modules.
The
UNRETURNED MSG COUNT values (one per communications channel) count the direct output messages that do not
make the trip around the communications ring. The CRC FAIL COUNT values (one per communications channel) count the
direct output messages that have been received but fail the CRC check. High values for either of these counts can indicate
on a problem with wiring, the communication channel, or one or more relays. The
UNRETURNED MSG COUNT and CRC FAIL
COUNT
values can be cleared using the CLEAR DIRECT I/O COUNTERS command.
The DIRECT INPUT 1 to DIRECT INPUT (32) values represent the state of each direct input.
6.3.16 Direct devices status
ACTUAL VALUES STATUS  DIRECT DEVICES STATUS
These actual values represent the state of direct devices 1 through 16.
6.3.17 EGD protocol status
6.3.17.1 Fast exchange
ACTUAL VALUES STATUS  EGD PROTOCOL STATUS PRODUCER STATUS FAST EXCHANGE 1
These values provide information for debugging an Ethernet Global Data (EGD) network. The EGD signature and packet size
for the fast EGD exchange display.
6.3.17.2 Slow exchange
ACTUAL VALUES STATUS  EGD PROTOCOL STATUS PRODUCER STATUS SLOW EXCHANGE 1(2)
These values provide information for debugging an EGD network. The EGD signature and packet size for the slow EGD
exchanges display.
DIRECT INPUT 32:
On
DIRECT DEVICES
STATUS
DIRECT DEVICE 1
STATUS: Offline
Range: Offline, Online
DIRECT DEVICE 16
STATUS: Offline
Range: Offline, Online
FAST EXCHANGE 1
FAST EXCHANGE 1
SIGNATURE: 0
FAST EXCHANGE 1
DATA LENGTH: 0
SLOW EXCHANGE 1
SLOW EXCHANGE 1
SIGNATURE: 0
SLOW EXCHANGE 1
DATA LENGTH: 0