10 Zone LED Alarm Panel - Engineering Manual
37
6.8.2 - How to enter Walk Test
The walk test function allows check each Zone trigger, Zone tamper, Detector tamper, Control
Panel tamper, Bell Box tamper, Remote Keypad tamper. In order to verify that they are
functioning correctly. A tone is generated as each zone or tamper is activated (opened).
e.g. Trigger Zone and Zone tamper
·
Under Engineer code
·
Press key to Select Test System.
·
Press key to select Walk test.
Trigger zone 1, when a zone is successfully tested,
the LED is on, Zones are added to list as each one
is activated.
·
Trigger detector tamper and its appropriate led will
light.
·
The Tamper LED comes on when tested.
·
Press key to exit current level.
6.8.3 - How to Exit Engineer Program Menu
·
··
·
Under Engineer menu.
·
··
·
Press key return to top of engineer menu.
·
··
·
Press key to exit engineer program mode.
and check system faults (all Tamper, TA zone,
PA zone, Fire zone is open)
·
··
·
When no fault, press any key to exit.
·
··
·
Return to DAY mode.
8
Day
PA
TAMP
1
2
3
4
5
6
7
8
9
10
8
R ES TE
Day
PA
TAMP
1
2
3
4
5
6
7
8
9
10
R ES TE
R ES TE
Day
PA
TAMP
1
2
3
4
5
6
7
8
9
10
Day
PA
TAMP
1
2
3
4
5
6
7
8
9
10
Day
PA
TAMP
1
2
3
4
5
6
7
8
9
10
Exit hint tone
Day
PA
TAMP
1
2
3
4
5
6
7
8
9
10
Day
PA
TAMP
1
2
3
4
5
6
7
8
9
10
Day
PA
TAMP
1
2
3
4
5
6
7
8
9
10