6. Troubleshooting and check
6-3
Over-error of
position
tracking
Abrupt
acceleration/deceleration,
gain set value error,
command pulse over-
frequency
(300kpps or above), mis-
wring, mechanical overload
Adjust position gain, increase menu
(P05-09) set value, adjust command
pulse frequency, check motor and
encoder wiring.
Check motor wiring, replace servo
drive
Encoder pulse
rate setting
error
Accurately set the encoder ID
(P01-12)
Absolute value
encoder data
transmission
error
Absolute value encoder
data transmission error
Re-transmit the absolute value
encoder data after resetting.
Battery voltage is 2.8V or
below
ABS encoder
multi turn data
transmission
error
ABS encoder multi turn
data transmission error
Re-transmit the absolute value
encoder data after resetting.
Output U, V, W mis-wiring
(Error Connection)
Check motor wiring, replace servo
drive
Battery LOW
Voltage Alarm
Battery voltage is lowered
below 3.1V
(When P02-35 = 1)
Battery (3.6V) replacement
After checking power system noise,
reset.
Replace drive if it still occurs
After checking power system noise,
reset.
Replace drive if it still occurs
Parameter initialization fail
High load long time driving,
Temperature rise in the
cabinet,
Temperature sensor failure
and cable removal
Check motor proper load, check
cooling in electric cabinet, replace
temperature sensor and cable,
check machine