10 Technical Data
10.1 General Information
dimensions/
housing
plug-in unit in 19technology, 3 height units
(3U), 1/3 or 1/2 housing width
depth without plug approx. 170 mm, with plugs
approx. 220 mm
process interfacing at the rear, operation
panel at the front
ambient conditions ambient temperature range 10 °C up to
+55 °C
humidity < 90
%, non-condensing
installation outside Ex zones 0, 1 and 2 only
IP protection class IP20
storage temperature −25 °C to +60 °C
weight (fully equipped)
1/3 device width: approx. 1.3 kg
1/2 device width: approx. 2.1 kg
power supply 24 V DC with a tolerance of -15
% and +20
%
(i.e. maximum permissible range 20.4 V DC to
28.8 V DC),
power consumption up to 12 W (typically 5 W)
optional: 230 V AC via external power supply
operation in conjunction with an
uninterruptable power supply is recommended
( chapter 6.2 Power Supply and Grounding,
p. 47)
display/operation
panel
4.3TFT color display with touch screen,
480×272 pixels RGB, LED background
lighting

Table of Contents

Other manuals for Honeywell enCore FC Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell enCore FC Series and is the answer not in the manual?

Honeywell enCore FC Series Specifications

General IconGeneral
BrandHoneywell
ModelenCore FC Series
CategoryDesktop
LanguageEnglish

Related product manuals