20 NFS2-3030 Listing Document — P/N LS10006-051NF-E:F2 5/19/2022
2 Operation
Following are the approved applications for the NFS2-3030:
Local Application
Emergency Relocation (paging, live and pre-recorded)
Emergency Communication (telephone)
Protected premises unit
Auxiliary
Central Station
Remote Station
Proprietary
Proprietary (Rec unit)
Communication transmission path
Coded
Non-coded
DACT, no line security
–Reverse Polarity
Other transmission technologies, no line security
Releasing
Cross Zone
NFPA 12 Co2 Fire Extinguishing Systems
NFPA 12A, Halon 1301 Fire Extinguishing Systems
NFPA 13, Sprinkler Systems
NFPA 15, Water Spray Systems
NFPA 16, Foam-water sprinkler and foam-water spray systems
NFPA 17, Dry Chemical Extinguishing Systems
NFPA 17A, Wet Chemical Extinguishing Systems
NFPA 72 Central Station (Automatic, Manual and Waterflow) Fire Alarm Systems
NFPA 72 Local (Automatic, Manual, Waterflow, and Sprinkler Supervisory) Fire Alarm Systems
NFPA 72 Auxiliary (Automatic, Manual and Waterflow) Fire Alarm Systems
NFPA 72 Remote Station (Automatic, Manual and Waterflow) Fire Alarm Systems
NFPA 72 Proprietary (Automatic, Manual and Waterflow) Fire Alarm Systems (Protected Premises Unit)
NFPA 2001, Clean Agent Fire Extinguishing Systems
Process Control, Non-critical
Regional Settings
Canada (see “Canadian Applications” on page 26)
Chicago
• Panel’s Drill and Signal Silence keys will not function
• Annunciator Control Modules and SLC modules given a drill or signal silence Mode or Type Code will not allow local drill or signal
silence initiation
• Events must be Acknowledged prior to system reset
Fire Alarm Event
Initiating Device Activation
• Produces a steady audible tone
• Turns on the Alarm relay(s) (TB4, TB1 and TB2, if switch enabled)
• Flashes the
FIRE ALARM LED (red)
• Displays a Type Code that indicates the type of fire alarm being generated
• Latches the control panel in alarm (condition must be corrected and a reset performed to clear the alarm state from the panel)
• Activates the General Alarm zone (Z000)
• Displays
FIRE ALARM in the status banner on the control panel, along with information specific to the device
• Sends an Alarm message to the LCD display, remote annunciators, history buffer, installed printers, and CRT-2s
• Initiates any Control-By-Event actions
• Starts timers such as Silence Inhibit and Auto Silence
• Sends a Alarm message to the proprietary receiver via the network, if applicable
NOTE: When operating as a Protected Premises Control Unit, the ONYXWORKS-WS is UL Listed for monitoring and control of fire, smoke
control, and mass notification devices.
NOTE: If the alarm event is initiated by a device with a waterflow type Code, the control panel will disable the Signal Silence key
and the Auto Silence Timer.

Other manuals for Honeywell Notifier NFS2-3030

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier NFS2-3030 and is the answer not in the manual?

Honeywell Notifier NFS2-3030 Specifications

General IconGeneral
BrandHoneywell
ModelNotifier NFS2-3030
CategoryControl Panel
LanguageEnglish

Related product manuals