204 SCS Series Manual — P/N 15712:L 7/18/16
Special Applications Multiple Smoke Control Station
History/Printer
Figure C.3 shows the printer output for enable/disable switch state changes.
Figure C.3 Event History Example: Activating the Enable Switch
Figure C.2 Programming Example 2: Secondary Panel, Highest Priority, Normally Disabled
Programming
Visual
Indicators Notes
ZL498 = OR(SCSDIS(A25)) Secondary SCS
Disabled
ZL498 will be active when the secondary’s
enable/disable switch is disabled.
ZL499 = OR(AUTO(A25)) -- Required for Multiple Smoke Control Systems
applications; monitors the Auto status of the SCS-8L
(designated as A25 in this example).
Address must be lower than that of the MSCS
Control Zone.
ZL500 = NOT(SCSDIS(A25)) Secondary SCS
Active
ZL500 identifies the MSCS Control Zone of the
secondary NCA-2. This logic zone will be active
when the secondary’s enable/disable switch is
enabled.
ZL501 = AND(ZL499, N1ZL499) -- Required to track if the SCS-8L is in Auto; must use
the next logic zone address after the MSCS Control
Zone of the secondary NCA-2.
N1ZL500 Primary SCS
Active
N1ZL500 identifies the MSCS Control Zone of the
primary NCA-2.
NCA-2 (N2)
Custom Graphics
Annunciator
SCS-8L
(A25)
User interface for
Secondary MSCS:
Enable/Disable switch
Control switches
Visual indicators
Secondary MSCS Panel
LDM-32
CLEARED ACTIVE MSCS CONTROL ZONE
10:10:28A WED NOV 13, 2013 ZL0500
ACTIVE MSCS CONTROL ZONE
10:10:24A WED NOV 13, 2013 ZL0500

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER SCS Series and is the answer not in the manual?

Honeywell NOTIFIER SCS Series Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER SCS Series
CategoryControl Unit
LanguageEnglish

Related product manuals