SCS Series Manual — P/N 15712:L 7/18/16 33
Smoke Control Station (SCS-8) The SCSSCE
3.1.2 SCS V4.0 Software Features
This manual describes versions 2.84 and 4.0 of the SCS-8/SCS-8L; the table below specifies which features are available only to version 4.0
and higher.
To use the version 4.0 features, the smoke control station must be connected to NFS2-3030, or NCA-2 running software V21 or higher.
3.2 Smoke Control Station (SCS-8)
Each SCS-8 has two rotary decimal switches for addressing and 8 dipswitches for mode configuration (see Figure 3.1). The rotary switches
and dipswitches are not on the SCE-8.
Each SCS-8SCE-8 module has eight independent switch groups that consist of the following (see Figure 3.1):
Miniature locking toggle switch - three position ON/AUTO/OFF (OPEN/AUTO/CLOSE)
Four annunciator protocol points (two control and two monitor)
Green On (Open) LED
Yellow Off (Closed) LED
Amber Trouble LED
Each SCS-8SCE-8 also has two LEDs and one momentary switch with the following functions (see Figure 3.1):
Green All Auto LED
Amber Manual
Local Acknowledge/Lamp Test momentary switch
NOTE:
1. Software Part Numbers 73631 and 73845 are not compatible with INA combinations after M2.7.
2. Part #SCSV2.84 is not compatible with FACP/INA combinations prior to M2.8.
3. NFS-320s, NFS2-640s, NFS-640s, NFS2-3030s, NFS-3030s, NCAs and NCA-2s are only compatible with software #SCS2.84 or higher.
(They are not compatible with any 73XXX series software versions.)
4. To use the SCS V4.0, NFS2-3030, and/or NCA-2 must be running software V21 or higher.
Table 3.2 SCS Features: V2.84 vs V4.0
Panel Feature (V21.0)
FSCS Mode A** FSCS Mode B**
SCS-8/8L V2.84 SCS-8/8L V4.0 SCS-8/8L V4.0
Independent Switch-group Operation
(See Appendix C.2, “Mode B Operation”)
No No Yes
Multiple Smoke Control Station No Yes Yes
Pairing No Yes No
Programmable Trouble Timer* No Yes Yes
SCS Logic Equation Operators* No Yes Yes
Enhanced Trouble Reporting* No Yes Yes
*See NFS2-3030/NCA-2 documentation.
**See NFS2-3030/NCA-2 documentation for mode setting.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER SCS Series and is the answer not in the manual?

Honeywell NOTIFIER SCS Series Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER SCS Series
CategoryControl Unit
LanguageEnglish

Related product manuals