SCS Series Manual — P/N 15712:L 7/18/16 41
Preliminary SCS-8SCE-8 Design Considerations The SCSSCE
3.4.9 Point Assignment
Each toggle switch group of an SCSSCE uses four EIA-485 proto-
col points (of the 64 available) to control and monitor a particular
fan or damper. Each of the four points is responsible for one of the
four capabilities listed in Switch Group Type (CON
ONOP
,
CON
OFFCL
, VER
ONOP
, VER
OFFCL
). When a switch group is
assigned a particular switch group type, only those protocol points
that mimic the capabilities of the switch group type are needed. The
other points for that particular switch group are unneeded. The only
other category for protocol points is unused. Unused protocol
points are associated with switch groups on an SCS or SCE that are
not being used. Only needed and unused EIA-485 protocol points
must be programmed in the FACP for each SCSSCE used.
Unneeded protocol points do not get programmed. See Section 3.9
“Programming” for information on programming FACPs and
annunciators for use with the SCSSCE. The numbering scheme for
each of the 64 points follows the format below:
Where N is one of the 16 toggle switches of the SCS-8SCE-8, as shown in Figure 3.5, or one of the 16 contacts of the SCS-8LSCE-8L.
Example: What is the point number for the CON
ONOP
point associated with toggle switch number 11?
Annunciator Point = [4x(11-1)+1] = 41
This information should be calculated for each switch group so that proper mapping between SCSSCE annunciator points and the FACP
control and monitor modules can be programmed. This information will also be used to assign software type IDs to each of the 64 annuncia-
tor points (see Section 3.9 “Programming”).
Each protocol point classified as needed will have a control or monitor module associated with it. The control module associated with the
CON
ONOP
protocol point is called the CON
ONOP
CM. The control module associated with the CON
OFFCL
protocol point is called the
CON
OFFCL
CM. The monitor module associated with the VER
ONOP
protocol point is called the VER
ONOP
MM. The monitor module associ-
ated with the VER
OFFCL
point is called the VER
OFFCL
MM.
Figure 3.5 Toggle Switch Group Numbering
Switch
Group 5
Switch
Group 6
Switch
Group 7
Switch
Group 8
Switch
Group 1
Switch
Group 2
Switch
Group 3
Switch
Group 4
Switch
Group 13
Switch
Group 14
Switch
Group 15
Switch
Group 16
Switch
Group 9
Switch
Group 10
Switch
Group 11
Switch
Group 12
CON
ONOP
Point Number for Switch N = [4 x (N-1) + 1]
Annunciator protocol output point used to turn on a fan or open a damper.
CON
OFF/CL
Point Number for Switch N = [4 x (N-1) + 2]
Annunciator protocol output point used to turn off a fan or close a damper.
VER
ONOP
Point Number for Switch N = [4 x (N-1) + 3]
Annunciator protocol input point used to monitor the on state of sail or limit switch contacts.
VER
OFFCL
Point Number for Switch N = [4 x (N-1) + 4]
Annunciator protocol input point used to monitor the off state of sail or limit switch contacts.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER SCS Series and is the answer not in the manual?

Honeywell NOTIFIER SCS Series Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER SCS Series
CategoryControl Unit
LanguageEnglish

Related product manuals