EasyManuals Logo
Home>Honeywell>Control Unit>NOTIFIER SCS Series

Honeywell NOTIFIER SCS Series User Manual

Honeywell NOTIFIER SCS Series
210 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #40 background imageLoading...
Page #40 background image
40 SCS Series Manual — P/N 15712:L 7/18/16
The SCSSCE Preliminary SCS-8SCE-8 Design Considerations
3.4.7 Dipswitch Setting
The eight dipswitches are used to control the function of the SCSSCE. The dipswitches perform the functions as listed in Table 3.4, where:
switches 1-5 control the combinations of switch group types; switch 6 controls whether the SCSSCE operates in the FSCS or the HVAC
mode; switch 7 selects Dedicated or Non-dedicated System operation when in the FSCS mode or enables/disables the Control-By-Event
lockout when manual operation is initiated in the HVAC mode; and switch 8 installs or removes the end-of-line termination resistor.
3.4.8 EIA-485 Addressing
The SCS-8 communicates with the FACP on the EIA-485 data line.
Each SCS-8 requires a unique address so that the FACP can properly
route data. There are 32 valid addresses in an FACP EIA-485 circuit
in ACS mode, numbered 1-32, and each address provides the SCS
with 64 points of monitor and control capability. Each SCS-8SCE-8
uses one EIA-485 protocol address and its respective point capacity
(64 points). The first 32 points are used for the SCS-8; the second 32
are used for the SCE-8.
Addressing the SCS-8 is accomplished by using the two rotary deci-
mal switches mounted on the SCS-8. The decimal switches must be
set to any of the available valid addresses (1-32) of the FACP. Each SCS-8 must be set to an address that is different than all other EIA-485
driven devices (annunciators, other SCS-8s, etc.).
The rotary switches are set by using a screwdriver to position the indicating mark on the rotary portion of the switch next to the desired digit.
For example, to set address 14, the 'TENS' switch is set to 1 and the 'ONES' switch is set to 4.
Table 3.4 SCS Dipswitch Mode Configurations
SWITCH
NUMBER
DESCRIPTION FUNCTION SWITCH LOCATION & POSITION
1 to 5 Selects which combination of control/monitor
modules are assigned to each SCS-8SCE-8
toggle switch group
See Table 3.5 on page 55 for
FSCS Mode.
See Table 3.10 on page 67 for
HVAC Mode.
6* Selects FSCS Mode or HVAC Mode for all 16
SCS-8SCE-8 toggle switch groups
ON = FSCS Mode
OFF = HVAC Mode
7* For FSCS Mode, selects Dedicated or Non-
dedicated System for all 16 SCS-8SCE-8
toggle switch groups
ON = Dedicated
OFF = Non-dedicated
For HVAC Mode, enables/disables Control-
By-Event lockout when manual operation is
initiated at the SCS-8SCE-8
ON = Enabled
OFF = Disabled
8 Installs or removes the built-in 120 ohm EIA-
485 end-of-line termination resistor (see
Figure 3.14)
ON = Installed
OFF = Removed
*Must be set “OFF” for INA, or when the SCS module is directly connected to the EIA-485 bus of an NFS-320, NFS2-640, or NFS-640
FACP.
Switch set to
"OFF" position
Switch set to
"ON" position
Switch Locations
Figure 3.4 SCS Address Switches
ONES
TENS
SCS-SWIT.wmf

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER SCS Series and is the answer not in the manual?

Honeywell NOTIFIER SCS Series Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER SCS Series
CategoryControl Unit
LanguageEnglish

Related product manuals