38 SCS Series Manual — P/N 15712:L 7/18/16
The SCSSCE Preliminary SCS-8SCE-8 Design Considerations
Usually a fan does not need the capability of separate verification of its on/off state (requiring two monitor modules). One monitor module is
capable of determining when the fan is on and when it is off.
3.4.5 Switch Group Type
Each controlled/monitored fan or damper has one associated switch group on the SCSSCE. Each switch group has four EIA-485 protocol
points used to control and monitor a fan or damper. There are four stand-alone capabilities available for controlling and monitoring fans and
dampers for smoke control:
The capability to turn a fan on (open a damper), regardless of its current state
The capability to turn a fan off (close a damper), regardless of its current state
Monitor and verify when the fan is on (or when damper is open)
Monitor and verify when the fan is off (or when damper is closed)
If a fan or damper requires all four of these capabilities, then two control modules and two monitor modules must be connected to the device
and one protocol point would be responsible for each of the four capabilities. A control module is assigned either an ONOPEN or an
OFFCLOSED capability to control a fan or damper.
ONOPEN Control (CON
ONOP
) - turn a fan on (or open a damper)
OFFCLOSED Control (CON
OFFCL
) - turn a fan off (or close a damper)
A monitor module is assigned an ONOPEN or an OFFCLOSED capability for verification of the state of a fan or damper.
ONOPEN Verification (VER
ONOP
) - verify when a fan is on (or verify when a damper is open)
OFFCLOSED Verification (VER
OFFCL
) - verify when a fan is off (or verify when a damper is closed)
These four capabilities, now referred to as CON
ONOP
, CON
OFFCL
, VER
ONOP
and VER
OFFCL
, can be applied to the nine scenarios as
shown in Table 3.3. These nine combinations represent all the capabilities a fan or damper can have for smoke control. The capabilities of
each fan or damper must match one of these nine scenarios. Each scenario is referred to as a switch group type.
Example: If a fan must have the capability of on and off control, as well as verification of when the fan is on, you would
need switch group type 8.
3.4.6 Switch Group Type Configuration
Once the switch group types have been selected, they must be configured for the SCSSCE. The configuration of switch group types will
determine the number of SCSSCE modules required for the system. The configuration layouts must be selected from pre-chosen formats
shown in the tables in Section 3.8 “Configuration”. Although the configurations in these tables are shown with an SCE, the configuration is
the same for the SCS if an SCE is not used.
Table 3.3 FSCS Mode Switch Group Types
1 CON
OFFCL
and VER
OFFCL
Turn a fan off (close a damper) and verify when the fan is off (damper closed)
2 CON
OFFCL
and VER
ONOP
Turn a fan off (close a damper) and verify when the fan is on (damper open)
3 CON
OFFCL
, VER
ONOP
and
VER
OFFCL
Turn a fan off (close a damper) and verify when the fan is on and off (damper open and closed)
4 CON
ONOP
and VER
OFFCL
Turn a fan on (open a damper) and verify when the fan is off (damper closed)
5 CON
ONOP
and VER
ONOP
Turn a fan on (open a damper) and verify when the fan is on (damper open)
6 CON
ONOP
, VER
ONOP
and
VER
OFFCL
Turn a fan on (open a damper) and verify when the fan is on and off (damper open and closed)
7 CON
ONOP
, CON
OFFCL
and
VER
OFFCL
Turn a fan on and off (open and close a damper) and verify when the fan is off (damper closed)
8 CON
ONOP
, CON
OFFCL
and
VER
ONOP
Turn a fan on and off (open and close a damper) and verify when the fan is on (damper open)
9 CON
ONOP
, CON
OFFCL,
VER
ONOP
and VER
OFFCL
Turn a fan on and off (open and close a damper) and verify when the fan is on and off (damper open and closed)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER SCS Series and is the answer not in the manual?

Honeywell NOTIFIER SCS Series Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER SCS Series
CategoryControl Unit
LanguageEnglish

Related product manuals