80 SCS Series Manual — P/N 15712:L 7/18/16
The SCSSCE Programming
When points are all mapped, return to the System Programming screen and click on the “ACS Address Maps” tab. Check the ACS box at
right. Enter the user-defined group number (User Map #) in the appropriate annunciator address box.
3.9.4 INA Programming (Legacy Systems)
The INA supports HVAC mode without manual control. With the INA, an SCS is programmed as an annunciator. Refer to the INA manual
for instructions.
The following programming notes apply:
When using an SCS connected to an INA:
Each point within a switch group (4 annunciator points) must be shadowed to the same fire alarm control panel.
When using the SCE connected to an INA with multiple fire panel mapping:
Loss of communications between the SCS and one of the control panels can cause failure of the entire SCSSCE annunciator. Do not use
this configuration if independent control is required.
3.9.5 AM2020/AFP1010 Programming (Legacy Systems)
Because the SCS Series Smoke Control Station works in conjunction with the AM2020/AFP1010 FACP, programming of the FACP is
required for proper operation of the SCS. The installer must program the FACP with the following information:
1. The appropriate EIA-485 device address for the SCS
2. The necessary EIA protocol points for the respective address, including software type ID
3. The required control and monitor modules, including control-by-event equations, software type ID, and EIA-485 protocol point
mapping
4. All inputs that will initiate smoke control must be mapped to Z240.
Each of the items above require the designer to enter the programming mode of the AM2020/AFP1010 FACP. In order to enter the program-
ming mode, the level 2 password for the FACP is necessary. The programming mode of the FACP is accessed by keying in the following
sequence on the keypad:
m } [
Once in the programming mode, the display will show the Main Programming Menu:
PRESS@1=PSYS,2=FSYS,3=PPRG,4=FPRG,5=REMV,6=PSWD,7=MSG,8=HIS
There are only three options that will be needed to program the FACP for the SCSSCE:
Enter the user-defined
group number into the box
of the annunciator address
it was created for.
Check the
ACS box
Figure 3.34 System Programming, ACS Address Maps Screen

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER SCS Series and is the answer not in the manual?

Honeywell NOTIFIER SCS Series Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER SCS Series
CategoryControl Unit
LanguageEnglish

Related product manuals