SCS-8SCE-8 Installation The SCSSCE
Back side of board
EIA-485 In (–)
EIA-485 Out (–)
EIA-485 Out (+)
EIA-485 In (+)
Not Used
Not Used
Common In (–)
Common Out (–)
Power In (+24 VDC)
Power Out (+24 VDC)
Earth Ground
Figure 3.13 SCS-8 Terminals
EIA-485 (–)
EIA-485 (+)
First SCS-8 or Annunciator _ _ _ _Last SCS-8
Dipswitch 8 ON
TB2
FACP/Network
Annunciator
EIA-485 (–)
EIA-485 (+)
FACP/Network
Annunciator
TB2
TB2
TB2
First SCS-8 or Annunciator _ _ __Last Annunciator
ELR installed
Terminate with
120 ohms if required.
+
+
+
+
+
+
+
+
ELR
Part #
71244
Figure 3.14 Wiring Two or More Smoke Control Stations (SCS-8)/Annunciators
Fire Alarm Control Panel
24 VDC Power
(12 to 18 AWG )
Two-wire EIA-485 Circuit
(Maximum of 6,000 feet)
SCS-8
Note: The
AM2020/AFP1010
control panels can
support two EIA-485
circuits, each capable
of spanning 6,000
feet @ 16 AWG
(refer to The
AM2020/AFP1010
Installation Manual).
Figure 3.15 EIA-485 and Power Wiring

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER SCS Series and is the answer not in the manual?

Honeywell NOTIFIER SCS Series Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER SCS Series
CategoryControl Unit
LanguageEnglish

Related product manuals