24
Technical data 230V (size 13 to 23)*
The recommended motor rating is for 4/6 pole standard motors. When using motors with different
numbers of poles, the inverter must be dimensioned based on the motor rated current. Contact
the manufacturer for special frequency motors.
The power rating of the inverter must be de-rated for operation above 3,300 ft (1000 m). Reduce
the rated power 1% for each additional 330 ft (100 m). The maximum elevation for operation is
6,560 ft (2000 m)
i
Inverter Size
13
14 15
16
17
Max Motor Power
[hp] 7. 5
10 15 20 25
Housing Size
E E
G G H H
Unit Hardware
B B
B D B B D
InputInput Ratings
Supply voltage [V] 180...260 +/- 0 (240V Nominal Voltage)
Supply voltage frequency [Hz] 50 / 60 +/- 2
Input phases
3
3 3 3 3 3
Rated input current
[A] 28
36 52 63 92
UL minimum wire gauge
1)
[awg] 24
24 16 16 12 12
UL maximum wire gauge
1
[awg] 10
10 4 4 0 0
Output Ratings
Rated output power [kVA] 9.5 13 19 26 33
Rated motor power [kW] 5.5 7. 5 11 15 18.5
Rated output current
[A] 22
28 42 57 84
Peak current (30 seconds)
2)
[A] 36 49.5 72 86 118 151 168
Over current fault (E.OC) trip level [A] 43 59 86 104 142 181 201
Output voltage [V] 3 x 0...V input (3 x 0...255V
2)
)
Output frequency [Hz] Generally 0 to 599Hz (limited by control board and carrier frequency)
Rated switching frequency
3)
[kHz] 8 4 8 4 16 4 4
Maximum switching frequency [kHz] 16 16 16 16 16 16 16
Power loss at rated operation
4)
[W] 290 350 420 420 550 850 850
Stall current at 4kHz [A] 24 33 36 60 73 126 118
Stall current at 8kHz [A] 24 24 31 53 73 109 97
Stall current at 16kHz [A] 16.8 16.8 26 43 73 92 59
Braking Circuit
Min. braking resistance[Ohm] 16 16 8.0 5.6 4.5 4.5
Typ. braking resistance[Ohm] 27 20 13 13 10 7. 0
Max. braking current [A] 25 25 50 70 90 90
Installation Information
Max. shielded motor cable length
5)
[ft] 330 330 330 330 330
Tightening torque for power terminals [in lb] 11 11 11 35 35
Environmental
Max. heat sink temperature TOH [°C] 90°C / 194°F
Storage temperature [°C] -25...70 °C / -13…158°F
Operating temperature [°C] -10...45 °C / 14…113°F
Housing design / protection Chassis / IP20 / Pollution Degree 2
Relative humidity max. 95% without condensation
Approvals
Tested in accordance with… EN 61800-3 /UL508C
Standards for emitted interference EN 55011 Class B / EN 55022 Class A
Standards for noise immunity IEC 1000-4-2 / -3 / -4 / -5/ -6
Climatic category 3K3 in accordance with EN 50178
*Smaller sizes available
1.4. Technical data 230V (size 13 to 23)*