Customizing Defaults
A pre-saved parameter le can be used to create custom defaults settings.
The pre-saved parameter le can either be created using the Combivis
computer program or taken as an upload from a drive already programmed.
The le type needs to be .dw5.
The .dw5 le must then be saved to the keypad operator ash memory.
The .dw5 le must be transferred via FTP.
To save the custom parameter list text le to ash, OEM password level is
required. From the Programming Menu, the ‘File option (F4) will then be listed.
Under the ‘File list, select ‘File Operations. Under ‘File Operations select
‘FTP’(F2) When the .dw5 le has been transferred to the keypad operator ash
memory, select ‘Menu’ (F1), then ‘Prog’ (F1) to return to the Programming Menu.
To load the .dw5 parameter le to the keypad operator, set CH03 Restore
Parameters = Load Motor Data.
To save the current settings as the new defaults, set US05 = Create OEM
Default.
To revert to the custom .defaults, set CH03 = Factory Reset or US05 = Restore
OEM Defaults
3.10. Customizing
Defaults

Table of Contents

Other manuals for KEB COMBIVERT F5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F5 and is the answer not in the manual?

KEB COMBIVERT F5 Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT F5
CategoryDC Drives
LanguageEnglish

Related product manuals