Technical data 480V (size 13 to 28)*
i
The recommended motor rating is for 4/6 pole standard motors. When using motors with different
numbers of poles, the inverter must be dimensioned based on the motor rated current. Contact
the manufacturer for special frequency motors.
The power rating of the inverter must be de-rated for operation above 3,300 ft (1000 m). Reduce
the rated power 1% for each additional 330 ft (100 m). The maximum elevation for operation is
6,560 ft (2000 m)
Inverter Size 13 14 15 16 16 17 17 18 19
Max Motor Power [hp] 7. 5 10 15 20 15 25 18.5 30 40
Housing Size E E E G H G H H H
Unit Hardware
B B B B B B B B B
Input Ratings
Supply voltage [V] 305...528 ±0 (480 V Nominal voltage
)
Supply voltage frequency [Hz] 50 / 60 +/- 2
Input phases 3 3 3 3 3 3 3 3 3
Rated input current 400VAC [A] 17 23 31 43 43 55 55 65 66
(UL) Rated input current 480VAC [A] 15.4 19.6 27.3 35 35 44 44 52 57
UL minimum wire gauge
2)
[awg]
24
24 24 16 8 16 6 12 12
UL maximum wire gauge
2)
[awg]
10
10 10 4 0 4 1/0 0 0
Output Ratings
Rated output power [kVA] 8.3 11 17 23 23 29 29 35 42
Rated motor power [kW] 5.5 7. 5 11 15 15 18.5 18.5 22 30
Rated output current 400VAC [A] 12 16.5 24 33 33 42 42 50 60
(UL) Rated output current 480VAC [A] 11 14 21 27 27 34 34 40 52
Peak current (30 seconds)
3)
[A] 21.6 29.7 36 49.5 49.5 63 63 75 90
Over current fault (E.OC) trip level [A] 25.9 35.6 43.2 59.4 59 75.6 75 90 108
Output voltage [V] 3 x 0…Vsupply
Output frequency [Hz] Generally 0 to 599Hz (limited by carrier frequency)
Rated switching frequency
4)
[kHz] 8 8 4 8 16 4 8 8 8
Maximum switching frequency [kHz] 16 16 16 16 16 16 16 16 16
Power loss at rated operation
5)
[W] 250 320 350 310 490 360 470 610 540
Stall current at 4kHz [A] 12 16.5 24 33 41.91 42 42 60 60
Stall current at 8kHz [A] 12 16.5 16 21.5 33 21.5 42 50 54
Stall current at 16kHz [A] 12 10 10 9.5 19.8 - 25.2 30 36
Braking Circuit
Min. braking resistance [Ohm] 39 36 36 19 19 19 19 9 9
Typ. braking resistance [Ohm] 100 85 56 39 39 28 28 22 16
Max. braking current [A] 21 21 21 40 40 40 40 90 90
Installation Information
Max. shielded motor cable length
7)
[ft]
300 330 330 330 330 330 330 330
Tightening torque for power terminals [in lb] 4.5 4.5 11 11 35 11 35 35 35
Environmental
Max. heat sink temperature TOH [°C] 90°C / 194°F
Storage temperature [°C] -25...70 °C / -13…158°F
Operating temperature [°C] -10...45 °C / 14…113°F
Housing design / protection Chassis/IP20 /Pollution Degree 2
Relative humidity max. 95% without condensation
Approvals
Tested in accordance with… EN 61800-3 /UL508C
Standards for emitted interference EN 55011 Class B/EN 55022 Class A
Standards for noise immunity IEC 1000-4-2 / -3 / -4 / -5/ -6
Climatic category 3K3 in accordance with EN 50178
*Additional sizes available
1.5. Technical data 480V (size 13 to 28)*

Table of Contents

Other manuals for KEB COMBIVERT F5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F5 and is the answer not in the manual?

KEB COMBIVERT F5 Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT F5
CategoryDC Drives
LanguageEnglish

Related product manuals