DeneCP-Parameters
© KEB, 2015-07 COMBIVERT R6-N Page3.9 - 3
3
10
3.9 DeneCP-Parameters
If the development stage of a machine is completed, usually only a few parameters are required to adjust or
control the COMBIVERT. In order to simplify the handling and end-user documentation, as well as the security
against unauthorized access, there is the possibility to create an own user interface, the CP-Parameters. 37
parameters (CP.00 ... CP.36) are available for this, 36 parameters (CP.01 ... CP.36) can be assigned free.
3.9.1 Survey
Picture3.91 Denitionstructure
CP.0 / ud.1
ud.15
ud.17
ru.3
ud.16
ud.17
ru. 3
ud.16
ud.17
An.32
CP.1
CP.2
CP.36
440 330 200 100 500
ud.16
1
2
36
Application mode
Service mode
Reading /
writing
read-on-
ly
Drive
mode
Password
CP mode
Address
Set / norm
Address
Address
Set / norm
Set / norm
ud.15 determines the CP-Parameter to be processed. With ud.16 and ud.17theCP-Parameterisdenedbyits
address, the respective set and the display norm. Dependent on the adjusted password (CP.0 or ud.1)
- the adjusted parameter is directly displayed in the service mode
- the adjusted parameter is displayed as CP-Parameter in the CP mode
ParameterCP.0isnotcongurable,italwaysincludesthepasswordinput.ud.1isusedforpasswordinputifthe
inverter is in application or service mode.
ParameterswhicharenotpermissibleasCP-Parameters(e.g.ud.15...17andFr.1)areconrmedwith"data
invalid". Input of an invalid parameter address switches the parameter to "oFF" (-1). The corresponding CP-Pa-
rameter is not displayed in this setting.
3.9.2 Assignment of CP-Parameters

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT R6-N and is the answer not in the manual?

KEB COMBIVERT R6-N Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT R6-N
CategoryInverter
LanguageEnglish

Related product manuals