Field Wiring
42
Signal Module (SGM-1004A) Terminal Connections
Wire devices to terminals as shown in Figure 35 below. See Wiring Tables and Information on page 47, Appendix A:
Specifications on page 59 for specifications, and Appendix B: Compatible Devices on page 61 for compatible
devices.
Figure 34: Hardwire Signal Module Terminal Connections
Notes:
• The terminal blocks are “depluggable” for ease of wiring.
• All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.
• SGM-1004A indicating circuits are fully supervised and rated for 24 VDC unfiltered 1.7A max. They must be
wired as shown in the wiring tables on .
IND2+ (Z)
IND2- (Z)
IND2- (Y/Z)
SUPERVISED INDICATING CIRCUIT #2
INDICATION
CIRCUIT 1
(POWER
LIMITED)
IND1+ (Z)
STYLE Z
(CLASS A)
WIRING
IND1- (Y/Z)
IND1+ (Y/Z)
IND2+ (Y/Z)
IND1- (Z)
INDICATION
CIRCUIT 2
(POWER
LIMITED)
STYLE Y
(CLASS B)
WIRING
SUPERVISED INDICATING CIRCUIT #1
IND4+ (Z)
IND4- (Z)
IND4- (Y/Z)
SUPERVISED INDICATING CIRCUIT #4
INDICATION
CIRCUIT 3
(POWER
LIMITED)
IND3+ (Z)
STYLE Z
(CLASS A)
WIRING
IND3- (Y/Z)
IND3+ (Y/Z)
IND4+ (Y/Z)
IND3- (Z)
INDICATION
CIRCUIT 4
(POWER
LIMITED)
STYLE Y
(CLASS B)
WIRING
SUPERVISED INDICATING CIRCUIT #3
Leg en d: See Appendix B for compatible devices.
SMOKE DETECTOR
3.9K 1/2W ELR LISTED S5434
MODEL MP-300
MANUFACTURED BY MIRCOM