FX-2000 Series Installation and Operation Manual
53
System Reset Button
The System Reset button causes the Fire Alarm Control Panel, and all Circuits, to be reset
Resets all Latching, Trouble Conditions
Resets all Initiating Circuits
Resets 4-Wire Smoke Supply and Aux. Power Supply
Turns off all Indicating Circuits
Turns off Signal Silence, Ack & GA Indicators
Turns off Fire Drill
Stops and resets all Timers
Processes inputs as new events
Aux Disconnect is not affected
Reset cannot be activated until the Signal Silence Inhibit timer has expired.
Signal Silence Button
Activation of the Signal Silence button when the Panel is in Alarm, turns on the Signal Silence Indicator and
deactivates any Silenceable Indicating Circuits. Non-Silenceable Circuits are unaffected. Signals will re-sound upon
any subsequent Alarm. This button does not function during any configured Signal Silence Inhibit Timer period. It
also does not function if the Indicating Circuits are active as the result of a Fire Drill. In a Two Stage System, if the
Auto General Alarm Timer has timed out, this Signal Silence button also performs the same function as the
Acknowledge button.
Fire Drill Button
The Fire Drill button activates all programmed and non-Disconnected Indicating Circuits, but does not transmit any
Alarms via the City Tie, or Common Alarm Relay. Fire Drill may be programmed to operate specific Indicating
Circuits. Fire Drill is cancelled by pressing the button again (toggle switch), or if the Panel goes into a real Alarm.
Acknowledge Button (Two Stage Only)
If the Panel is not configured for Two Stage Operation, this button does nothing. If the Panel is configured for Two
Stage Operation, activation of the Acknowledge (2 STAGE AUTO CANCEL) button while the Auto General Alarm
Timer is timing (there is an Alarm in the Panel, but it is still in the First Stage), that timer is cancelled, and the
Acknowledge (2 STAGE AUTO CANCEL) Indicator is on steady amber.
General Alarm Button (Two Stage Only)
If the Panel is not configured for Two Stage Operation, this button does nothing. If the Panel is configured for Two
Stage Operation, activation of the General Alarm button immediately sends the Panel into Second Stage - General
Alarm. It will also re-activate the Signals if they have been Silenced during General Alarm. The General Alarm
condition remains active until the Panel is reset.
Lamp Test Button
Activation of the Lamp Test button turns all front panel Indicators on steady in whichever colour they would normally
be activated and turns the buzzer on steady. If Lamp Test is active for more than 10 seconds, Common Trouble is
activated.