α
2 Simple Application Controllers
AL2-2PT-ADP 12
ENG-70
12.4.6 Fine Offset Adjust
The fine adjust should only be performed after both Gain and Offset Adjusts have
been performed.
1) From the TopMenu, select “Others...”
2) From the “Others...” menu, select “Analog In”
3) From the Analog In menu select an input that is configured for PT100 input.
4) Select “Offset fine” from the Analog Input settings menu.
5) Using the + and - buttons, enter a value from -15.5°C to 15.5°C (-27.9°F to 27.9°F).
Press the OK button when finished.
TopMenu
ClockSet
LANGUAGE
Others. . .
Ot her s
Light Ti
Ana l og I
ProgCl ear
...
me
n
Ana l og I n
I01
I02:PT100
I03:TC
I02
Mo d e
Ca l i b r a t e
Of f se t f i ne
I02
0.0°C
Of f set f ine

Table of Contents