EasyManuals Logo
Home>Mitsubishi>Controller>MELSEC-F FX3U Series

Mitsubishi MELSEC-F FX3U Series User Manual

Mitsubishi MELSEC-F FX3U Series
242 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #106 background imageLoading...
Page #106 background image
B-52
7 Examples of Practical Programs
7.2 Program That Uses Convenient Functions
FX
3U
/FX
3UC
Series PLC User's Manual - Analog Control Edition
FX3UC-4AD (4-channel Analog Input)
7.2 Program That Uses Convenient Functions
This section describes a program that uses the convenient functions (BFM #22) of 4AD.
1. Conditions
The sequence program described in this section is created under the following conditions.
1) System configuration
4AD (unit No.1) should be connected to the main unit.
2) Input mode
Channels 1 and 2 should be set to mode 0 (voltage input, -10V to +10V -32000 to +32000).
Channels 3 and 4 should be set to mode 3 (current input, 4mA to 20mA 0 to 16000).
3) Number of averaging time
For all the channels, the number of averaging time should be set to "1" (default).
(To use the default value, it is not necessary to set the number of averaging time in the sequence
program.)
4) Digital filter function
For all the channels, the digital filter function should be disabled (default).
(To use the default value, it is not necessary to set the digital filter function in the sequence program.)
5) Convenient functions
The upper/lower limit detection function, upper/lower limit error status data automatic transfer function,
over-scale status data automatic transfer function, and error status data automatic transfer function
should be used.
6) Device assignment
Device Description
Input
X000 Clearance of upper/lower limit error data
X001 Clearance of over-scale data
X002 Clearance of error status data
Output
Y000 Output of channel-1 lower limit error data
Y001 Output of channel-1 upper limit error data
Y002 Output of channel-2 lower limit error data
Y003 Output of channel-2 upper limit error data
Y004 Output of channel-3 lower limit error data
Y005 Output of channel-3 upper limit error data
Y006 Output of channel-4 lower limit error data
Y007 Output of channel-4 upper limit error data
Y010 Output of channel-1 over-scale (lower limit) data
Y011 Output of channel-1 over-scale (upper limit) data
Y012 Output of channel-2 over-scale (lower limit) data
Y013 Output of channel-2 over-scale (upper limit) data
Y014 Output of channel-3 over-scale (lower limit) data
Y015 Output of channel-3 over-scale (upper limit) data
Y016 Output of channel-4 over-scale (lower limit) data
Y017 Output of channel-4 over-scale (upper limit) data
Y20 Output of error detection signal
Y21 Output of setting error detection signal
D0 A/D converted digital value of channel 1
D1 A/D converted digital value of channel 2
D2 A/D converted digital value of channel 3
D3 A/D converted digital value of channel 4
D100 Upper/lower limit error status data automatic transfer-to data register
D101 Over-scale status data automatic transfer-to data register
D102 Error status data automatic transfer-to data register

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC-F FX3U Series and is the answer not in the manual?

Mitsubishi MELSEC-F FX3U Series Specifications

General IconGeneral
BrandMitsubishi
ModelMELSEC-F FX3U Series
CategoryController
LanguageEnglish