A-25
4 Comparison of Performance Specifications
4.3 Analog Input/Output Mixture
A
Common Items
B
FX
3UC
-4AD
C
FX
3U
-4AD-ADP
D
FX
3U
-4DA-ADP
E
FX
3U
-4AD-PT
-ADP
F
FX
3U
-4AD-TC
-ADP
G
PID Instruction
(FNC 88)
FX
3U
/FX
3UC
Series PLC User's Manual - Analog Control Edition
Common Items
4.3.2 FX0N-3A
*1. Mixed use of voltage and current inputs is not possible.
*2. Use the adjustment volume to adjust FX
0N-3A.
*3. Adjustment of the offset or gain value will change the resolution.
Specifications
FX0N-3A
Voltage input Current input Voltage output Current output
Number of
input/output
points
2ch 1ch
Analog input/
output range
*1
0V to 10V DC
0V to 5V DC
(Input resistance: 200k)
4mA to 20mA DC
(Input resistance: 250)
0V to 10V DC
0V to 5V DC
(External load: 1k to 1M)
4mA to 20mA DC
(External load: 500)
Absolute
maximum
input
-0.5V,
+15V
-2mA,
+60mA
--
Offset
*2*3
If the digital value is "0":
0V to 1V
If the digital value is "0":
0mA to 4mA
If the digital value is "0":
0V to 1V
If the digital value is "0":
4mA
Gain
*2*3
If the digital value is "250":
5V to 10V
If the digital value is "250":
20mA
If the digital value is
"4000":
5V to 10V
If the digital value is
"4000":
20mA
Digital input/
output
0 to 250
8 bits, binary
0 to 250
8 bits, binary
Resolution
*3
40mV(10V×1/250) 64µA(16mA×1/250) 40mV(10V×1/250) 64µA(16mA×1/250)
Overall
accuracy
±0.1V ±0.16mA ±0.1V ±0.16mA
Time required
for conversion
TO instruction processing time × 2 + FROM instruction processing time
(operation synchronized with sequence program)
I/O
characteristics
If the input data consists of 9 bits or more, only the
lower 8 bits will be valid, and the other bits will be
ignored.
Insulation
method
The photocoupler is used to insulate the analog input and output area from the PLC.
Channels are not insulated from each other.
Number of I/O
occupied
points
8 points (Count either the input or output points of the PLC.)
0
250
10V
255
Analog input
Digital output
Approx. 10.200V
255
0
250
20mA
Analog input
Digital output
4mA
Approx. 20.320mA
0
10V
250
Digital input
Analog output
255
0
20mA
250
Digital input
Analog output
4mA
255

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC-F FX3U Series and is the answer not in the manual?

Mitsubishi MELSEC-F FX3U Series Specifications

General IconGeneral
BrandMitsubishi
ModelMELSEC-F FX3U Series
CategoryController
LanguageEnglish

Related product manuals