NFS2-3030 Operations Manual — P/N 52546:N1 06/20//2014 47
Mass Notification Trouble Event Operation of the Control Panel
Figure 2.12 Sample Message for MN Trouble
2.11.2 How to Respond to a Mass Notification Trouble
If the control panel indicates a trouble, the operator can do the following:
1. Press the ACKNOWLEDGE
soft key to silence the panel sounder and switch the SYSTEM TROUBLE
LED from flashing to steady—regardless of the number of troubles, alarms, security and
supervisory signals.
The control panel sends an acknowledge message to the History buffer, installed printers and
annunciators.
2. Check the trouble message for an indication of the trouble.
Press the MORE INFORMATION soft key to display the MORE INFORMATION screen and
view additional information on the device and possibly preprogrammed text for recommended
action. (Refer to Figure 1.8 on page 19 for an example of the this screen and an explanation of
its fields.)
3. Correct the condition causing the trouble. If the trouble clears, the control panel sends a Clear
Trouble message to the History buffer, installed printers and annunciators.
If all troubles clear and no supervisory signals or fire alarms exist, the control panel does the fol-
lowing:
Returns to Normal operation (indicated by the “System Normal” message)
Sends a “System Normal” message to the panel display, History buffer, installed printers and
annunciators
Restores troubles automatically - even if troubles are not acknowledged
The soft key PROGRAM/ALTER STATUS is also displayed on this screen. A password is required
to enter these menus, which are described in this panel’s programming manual.
MN TROUBLE DETECTOR FAILED TEST
SECURITY DESK MAIN BLDG
FIRST FLOOR MN TMON
11:58:45A TUE JAN 22, 2013 L01M136
EVENT COUNTS
FIRE ALARMS:000 PREALARM:000 TROUBLE:001
SUPERVISORY:000 SECURITY:000 DISABLE:000
11:59:35A TUE JAN 22, 2013
ACKNOWLEDGE SIGNAL SILENCE
MORE INFORMATION SYSTEM RESET
PROGRAM/ALTER STATUS MAIN MENU

Other manuals for Notifier NFS2-3030

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier NFS2-3030 and is the answer not in the manual?

Notifier NFS2-3030 Specifications

General IconGeneral
BrandNotifier
ModelNFS2-3030
CategoryControl Panel
LanguageEnglish

Related product manuals