NFS2-3030 Operations Manual — P/N 52546:N1 06/20//2014 59
General Zone Read Status
3.8 General Zone
When a general zone address is entered into the Point Select Screen and the ACCEPT soft key is
pressed, the following screen will display:
Figure 3.9 General Zone Screen - Read Status
Display
Lines 1 through 7 - Refer to the descriptions in Section 3.2, “Smoke Detector”, on page 52.
Line 8 - The non-resettable control setting for this zone is displayed on this line.
Line 9 - The silenceable setting for this zone is displayed on this line.
Line 15 - the current time and date
3.9 Logic Zone
When a logic zone address is entered into the Point Select Screen and the ACCEPT soft key is
pressed, the following screen will display:
Figure 3.10 Logic Zone Screen - Read Status
LAKEVIEW GENERAL HOSPITAL
SYSTEM NORMAL
10:22:34A TUE JAN 25, 2011
READ ADDRESS: N124Z066
AUTOMATIC INACTIVE
66TH FLOOR Z066
NON-RESETTABLE CONTROL: NO
SILENCEABLE: NO
PRECEDENCE PARTICIPATION: NO
10:22:34A TUE JAN 25, 2011
BACK
LAKEVIEW GENERAL HOSPITAL
SYSTEM NORMAL
10:22:34A TUE JAN 25, 2011
READ ADDRESS: N124ZL0066
AUTOMATIC INACTIVE
LOGIC ZONE NUMBER 66 ZL0066
EQUATION:
AND(L1D1,L2D1)
10:22:34A TUE JAN 25, 2011
BACK