198
Basic Ladder Diagrams Section 4-3
If IR 00000 is ON in the revised version of diagram B, above, the status of IR
00001 and that of IR 00002 would determine the execution conditions for
instructions 1 and 2, respectively. Because IR 00000 is ON, this would pro-
duce the same results as ANDing the status of each of these bits. If IR 00000
is OFF, the INTERLOCK instruction would produce an OFF execution condi-
tion for instructions 1 and 2 and then execution would continue with the
instruction line following the INTERLOCK CLEAR instruction.
As shown in the following diagram, more than one INTERLOCK instruction
can be used within one instruction block; each is effective through the next
INTERLOCK CLEAR instruction.
If IR 00000 in the above diagram is OFF (i.e., if the execution condition for the
first INTERLOCK instruction is OFF), instructions 1 through 4 would be exe-
cuted with OFF execution conditions and execution would move to the instruc-
tion following the INTERLOCK CLEAR instruction. If IR 00000 is ON, the
status of IR 00001 would be loaded as the execution condition for instruction 1
and then the status of IR 00002 would be loaded to form the execution condi-
tion for the second INTERLOCK instruction. If IR 00002 is OFF, instructions 2
through 4 will be executed with OFF execution conditions. If IR 00002 is ON,
IR 00003, IR 00005, and IR 00006 will determine the first execution condition
in new instruction lines.
4-3-9 Jumps
A specific section of a program can be skipped according to a designated exe-
cution condition. Although this is similar to what happens when the execution
condition for an INTERLOCK instruction is OFF, with jumps, the operands for
all instructions maintain status. Jumps can therefore be used to control
devices that require a sustained output, e.g., pneumatics and hydraulics,
whereas interlocks can be used to control devices that do not required a sus-
tained output, e.g., electronic instruments.
Instruction 1
00002
00000
Instruction 2
00001
ILC(03)
IL(02)
Address Instruction Operands
00000 LD 00000
00001 IL(02) ---
00002 LD 00001
00003 Instruction 1
00004 LD 00002
00005 Instruction 2
00006 ILC(03) ---
Instruction 1
00000
Instruction 2
00001
ILC(03)
IL(02)
00004
Instruction 3
Instruction 4
00006
00005
00003
00002
IL(02)
Address Instruction Operands
00000 LD 00000
00001 IL(02) ---
00002 LD 00001
00003 Instruction 1
00004 LD 00002
00005 IL(02) ---
00006 LD 00003
00007 AND NOT 00004
00008 Instruction 2
00009 LD 00005
00010 Instruction 3
00011 LD 00006
00012 Instruction 4
00013 ILC(03) ---