AR Area Section 3-6
3-6-2 Flags/Bits for Inner Boards (AR 05 and AR 06)
High-speed Counter Board Slot 2 Flags/Bits (AR 05 to AR 06)
Pulse I/O Board Slot 2 Flags/Bits (AR 05 to AR 06)
Word Bit(s) Function Operation
AR 05 00 High-speed Counter 1 Reset Bit Z Phase and software reset
0: Z-phase reset disabled
1: Z-phase reset enabled
Software reset only
0: Software reset disabled
0→1: Executes software reset
01 High-speed Counter 2 Reset Bit
02 High-speed Counter 3 Reset Bit
03 High-speed Counter 4 Reset Bit
04 to 07 Not used. ---
08 High-speed Counter 1 Comparison Stop Bit 0→1: Starts comparison.
1→0: Stops comparison.
09 High-speed Counter 2 Comparison Stop Bit
10 High-speed Counter 3 Comparison Stop Bit
11 High-speed Counter 4 Comparison Stop Bit
12 High-speed Counter 1 Stop Bit 0: Continues operation.
1: Stops operation.
13 High-speed Counter 2 Stop Bit
14 High-speed Counter 3 Stop Bit
15 High-speed Counter 4 Stop Bit
AR 06 00 External Output 1 Force-set Bit 0: Not valid
1: Forced ON
01 External Output 2 Force-set Bit
02 External Output 3 Force-set Bit
03 External Output 4 Force-set Bit
04 External Output Force-set Enable Bit 0: Force-setting of outputs 1 to 4 disabled
1: Force-setting of outputs 1 to 4 enabled
05 to 15 Not used. ---
Word Bit(s) Operation
AR 05 00 to 07 High-speed Counter 1 Range Comparison Flags
Bit 00 ON: Counter PV satisfies conditions for comparison range 1
Bit 01 ON: Counter PV satisfies conditions for comparison range 2
Bit 02 ON: Counter PV satisfies conditions for comparison range 3
Bit 03 ON: Counter PV satisfies conditions for comparison range 4
Bit 04 ON: Counter PV satisfies conditions for comparison range 5
Bit 05 ON: Counter PV satisfies conditions for comparison range 6
Bit 06 ON: Counter PV satisfies conditions for comparison range 7
Bit 07 ON: Counter PV satisfies conditions for comparison range 8
08 High-speed Counter 1 Comparison Flag
OFF: Stopped
ON: Comparing
09 High-speed Counter 1 Overflow/Underflow Flag
OFF: Normal
ON: Overflow or underflow occurred.
10 to 11 Not used.
12 to 15 Port 1 Pulse Output Flags
Bit 12 ON: Deceleration specified. (OFF: Not specified.)
Bit 13 ON: Number of pulses specified. (OFF: Not specified.)
Bit 14 ON: Pulse output completed. (OFF: Not completed.)