12
I/O Configuration and Main Functions Section 1-2
Model Number Structure
Model Number Legends
Note Silver is available by special order only.
1-2-2 Main Functions
This section introduces the main E5CN/CN-U/AN/EN/GN functions. For
details on particular functions and how to use them, refer to SECTION 3 Basic
Operation and following sections.
Input Sensor Types • The following input sensors can be connected for temperature input
(i.e., E5_N-@@@@T):
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, PLII
Infrared temperature sensor: ES1B
10 to 70°C, 60 to 120°C, 115 to 165°C,
140 to 260°C
Platinum resistance thermometer: Pt100, JPt100
Analog input: 0 to 50 mV
Controllers
1. Control Output 1
R: Relay output
Q: Voltage output (for driving SSR)
C: Current output
2. Auxiliary Outputs
Blank: None
1: One outputs
2: Two outputs
3. Option
Blank: None
01: RS-232C communications
03: RS-485 communications
B: Two event inputs
H: Heater burnout/Heater short/Heater overcurrent
detection (CT1)
4. Input Type
T: Universal thermocouple/platinum resistance
thermometer input
L: Analog current/voltage input
5. Power Supply Voltage
Blank: 100 to 240 VAC
D: 24 VAC/VDC
6. Terminal Type
Blank: Models with Screw Terminal Blocks
C: Models with Screwless Clamp Terminal Blocks
7. Case Color
Blank: Black
W: Silver
8. Communications Protocol
Blank: None
FLK: CompoWay/F communications
1 2
E5GN-@@@@@-@-@-@
3 4 5 6 7 8