159
Protect Level Section 5-2
5-2 Protect Level
Four levels of protection are provided on the E5@N, operation/adjustment pro-
tect, initial setting/communications protect, setting change protect, and PF key
protect (E5AN/EN only). These protect levels prevent unwanted operation of
the keys on the front panel in varying degrees.
To move from the operation level to the protect level, press O and M Keys for
three seconds (see note) or more.
Note The time taken to move to the protect level can be adjusted by changing the
Move to Protect Level Time parameter setting.
Parameters that are protected will not be displayed and their settings cannot
be changed.
Control in Progress
Operation
Level
Adjustment
Level
Protect
Level
Power ON
Press the
O Key less than 1 s.
Press the O + M
Keys for at least 1 s.
Press the O + M keys;
display will flash.
Press the O + M Keys
for at least 3 s. (See
note.)
25
100
C
Protect Level
M
M
M
M
M
M
M
pmov
0
oapt
0
icpt
1
wtpt
off
pmsk
on
prlp
0
pfpt
off
Page
Move to Protect Level
Displayed only when a password
is set.
Operation/Adjustment
Protect
Initial Setting/
Communications Protect
Setting Change Protect
Parameter Mask Enable
Password to Move to
Protect Level
PF Key Protect
160
160
160
161
161
162
161