5 - 7
5 Advanced Operations
E5@C Digital Temperature Controllers User’s Manual (H174)
5-3 Executing Heating/Cooling Control (Not Supported for Position-proportional
Models.)
5
5-3-1 Heating/Cooling Control
5-3 Executing Heating/Cooling Control
(Not Supported for
Position-proportional Models.)
Heating/cooling control can be used with control output 2 and auxiliary outputs 1 to 4. Heating/cooling
control operates when h-c (heating/cooling) is selected for the Standard or Heating/Cooling parameter.
The following functions are assigned to outputs in the default status.
Each output assignment is automatically initialized as shown below when changing between standard
and heating/cooling control.
Assigned Output Functions
Digital Controllers with Three or Fewer Auxiliary Outputs
Digital Controllers with Four Auxiliary Outputs
5-3-1 Heating/Cooling Control
Parameter name Display Initial status
Control Output 1 Assignment out1 Control output for heating
Control Output 2 Assignment (E5CC,
E5EC, and E5AC only)
out2 Not assigned.
Auxiliary Output 1 Assignment sub1
Alarm 1
*1
Auxiliary Output 2 Assignment sub2 Alarm 2
Auxiliary Output 3 Assignment (E5CC,
E5EC, E5EC-B, and E5AC Only)
sub3 Alarm 3
Auxiliary Output 4 Assignment (E5EC,
E5EC-B, and E5AC Only)
sub4 Alarm 4
Parameter name Display
Without control output 2 With control output 2
Standard Heating/cooling Standard Heating/cooling
Control Output 1
Assignment
out1
Control output
(heating)
Control output
(heating)
Control output
(heating)
Control output
(heating)
Control Output 2
Assignment
out2 --- --- Not assigned.
Control output
(cooing)
Auxiliary Output 1
Assignment
sub1
Alarm 1
*1
Alarm 1
*1
Alarm 1
*1
Alarm 1
*1
Auxiliary Output 2
Assignment
sub2 Alarm 2
Control output
(cooing)
*2
Alarm 2 Alarm 2
Auxiliary Output 3
Assignment
sub3 Alarm 3 Alarm 3 Alarm 3 Alarm 3
Parameter name Display
Without control output 2 With control output 2
Standard Heating/cooling Standard Heating/cooling
Control Output 1
Assignment
out1
Control output
(heating)
Control output
(heating)
Control output
(heating)
Control output
(heating)
Control Output 2
Assignment
out2 --- --- Not assigned.
Control output
(cooing)

Table of Contents

Other manuals for Omron E5GC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5GC and is the answer not in the manual?

Omron E5GC Specifications

General IconGeneral
BrandOmron
ModelE5GC
CategoryTemperature Controller
LanguageEnglish

Related product manuals