6 - 39
6 Parameters
E5@C Digital Temperature Controllers User’s Manual (H174)
6-6 Manual Control Level
6
6-6 Manual Control Level
If you change to Manual Mode, the Manual MV parameter will be displayed and the displayed value will
be output as the MV.
For details on the setting method, refer to 5-12 Performing Manual Control.
• The MANU indicator will light during manual control.
• It is not possible to move to any parameters except for the PV/MV parameter during manual
operation.
a-m
Press the O Key for at
least 1 s; display will flash.
Operation
Level
Power ON
Adjustment
Level
Press the O Key
for less than 1 s.
Press the S Key
for at least 1 s. *
Manual Control Level
Press the O Key for
at least 3 s.
Press the S Key for
at least 1 s or the O
Key for at least 1 s.
*Here, the PF Setting parameter is set to A-M.