2 Preparations
2 - 52
E5@C Digital Temperature Controllers User’s Manual (H174)
Terminal Arrangement
The terminals block of the E5GC is divided into five types of terminals: control output 1, sensor input, auxiliary
outputs, input power supply, and options.
Precautions for Correct Use
When you purchase the Digital Controller, it will be set for a K thermocouple (input type = 5). If a
different sensor is used, an input error (s.err) will occur. Check the setting of the Input Type
parameter.
Model Numbers
The specification for control output 1 is given in the following location in the model number.
Terminal Details
2-2-8 E5GC Terminal Block Wiring Example
Control Output 1
Code Output type Specification
RX 1 relay output 250 VAC, 2 A (resistive load)
QX 1 voltage output (for driving SSR) 12 VDC, 21 mA
CX 1 linear current output 4 to 20 mA DC or 0 to 20 mA DC with load of 500 Ω max.
RX QX CX
Input power supply Control output 1
Auxiliary outputs
I
JKLGH
CDEFAB
Sensor inputOptions
E5GC-@@ @ @ @ M-@@@
Control output 1
Relay output
CD
Control
output 1
+
Control
output 1
CD
Voltage output
(for driving SSR)
+
Control
output 1
CD
Linear current output

Table of Contents

Other manuals for Omron E5GC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5GC and is the answer not in the manual?

Omron E5GC Specifications

General IconGeneral
BrandOmron
ModelE5GC
CategoryTemperature Controller
LanguageEnglish

Related product manuals