6 Parameters
6 - 38
E5@C Digital Temperature Controllers User’s Manual (H174)
6-5 Monitor/Setting Item Level
Monitor/setting items can be displayed by means of the function key when the PF Setting parameter
(Advanced Function Setting Level) is set to PFDP: Monitor/Setting Item.
pfd1 to 5
Monitor/Setting Item Display 1 to 5
The PF Setting parameter must be set to PFDP, and
the Monitor/Setting Item 1 to 5 parameters must not
be set to OFF.
• When the PF Key is set to display monitor/setting items, pressing the PF Key will display
in order the contents of the Monitor/Setting Item 1 to 5 parameters. The contents of these
parameters are shown in the following table. For the setting (monitor) ranges, refer to the
applicable parameters.
*1 With the E5CC, E5CC-U, E5CC-B, E5DC, E5DC-B, or E5GC, only the PV and SP can be
displayed.
*2 The Alarm Value 1 parameter is displayed even if the Alarm 1 Type parameter is set for no
alarm. However, any value that is set is not valid.
000
Operation
Level
Power ON
Adjustment
Level
Monitor/Setting
Item Level
Control in progress
Press the O Key
for less than 1 s.
S
Key
S
Key
Set value Setting
Remarks
Monitor/Setting Display
0 Disabled --- ---
1 PV/SP/Multi-SP
Can be set. (SP)
*1
---
2 PV/SP/MV (valve opening for
Position-proportional Models)
Can be set. (SP)
*1
---
3 PV/SP /Soak time remain
Can be set. (SP)
*1
---
4 Proportional band (P) Can be set. p
5 Integral time (I) Can be set. i
6 Derivative time (D) Can be set. d
7 Alarm value 1 Can be set. al-1
8 Alarm value upper limit 1 Can be set. al1h
9 Alarm value lower limit 1 Can be set. al1l
10 Alarm value 2 Can be set. al-2
11 Alarm value upper limit 2 Can be set. al2h
12 Alarm value lower limit 2 Can be set. al2l
13 Alarm value 3 Can be set. al-3
14 Alarm value upper limit 3 Can be set. al3h
15 Alarm value lower limit 3 Can be set. al3l
16 Alarm value 4 Can be set. al-4
17 Alarm value upper limit 4 Can be set. al4h
18 Alarm value lower limit 4 Can be set. al4l
19 PV/SP/Internal SP
Can be set. (SP)
*1
---
20
PV/SP/Alarm Value 1
*2
Can be set. (SP)
*1
---
21 Proportional Band (Cooling) Can be set. c-p
22 Integral Time (Cooling) Can be set. c-i
23 Derivative Time (Cooling) Can be set. c-d

Table of Contents

Other manuals for Omron E5GC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5GC and is the answer not in the manual?

Omron E5GC Specifications

General IconGeneral
BrandOmron
ModelE5GC
CategoryTemperature Controller
LanguageEnglish

Related product manuals