2 - 9
2 Preparations
E5@C Digital Temperature Controllers User’s Manual (H174)
2-1 Installation
2
2-1-3 Mounting
There are two models of Terminal Covers that you can use with the E5CC.
For the Wiring Socket for the E5CC-U, purchase the P2CF-11 or PG3A-11 separately.
Mounting to the Panel
(1) For waterproof mounting, waterproof packing must be installed on the Digital Controller.
Waterproofing is not possible when group mounting several Digital Controllers. The
E5CC-U cannot be waterproofed even if the Waterproof Packing is inserted.
(2) Insert the E5CC, E5CC-B, or E5CC-U into the mounting hole in the panel.
(3) Push the Adapter from the terminals up to the panel, and temporarily fasten the E5CC,
E5CC-B, or E5CC-U.
(4) Tighten the two fastening screws on the Adapter. Alternately tighten the two screws little by
little to maintain a balance. Tighten the screws to a torque of 0.29 to 0.39 N·m.
2-1-3 Mounting
E5CC, E5CC-B, and E5CC-U
Adapter
Waterproof packing
Panel
E53-COV17
Terminal Cover
(Sold separately.)
Adapter
E53-COV23
Terminal Cover*
* The Terminal Cover is provided only with
the following models:
E5CC-@@@@5M-@@@.