500-8067.9 * INSTALLATION AND OPERATING INSTRUCTIONS 8DJH * Revision 03 83
Installation
13 Electrical connections
13.1 Connecting high-voltage cables
For common features and suitable cable sets (see Page 27, "Cable connection").
ATTENTION!
The high-quality joints at the bushings can easily be damaged by incorrect handling.
Ö Observe extreme cleanliness.
Ö Avoid damages caused by the threaded bolt while pushing on.
ATTENTION!
If there are any spare feeders without connected cables, please observe the following:
Ö Switch the three-position switch to "EARTHED" position and lock it.
Ö Alternatively: Mount surge-proof caps.
ATTENTION!
During metal work, please ensure the following:
Ö Do not drill into the vessel.
Ö Do not leave any metal cuttings on the vessel in order to avoid rust layers.