S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
11-14 A5E00105492-03
(YHQWUHFRJQLWLRQ
The table below shows how CPU 31x-2 operating as DP master recognizes
operating mode transitions of a CPU operating as DP slave or data exchange
interruptions.
Table 11-8 Event recognition by CPUs 31x-2 as the DP master
(YHQW :KDWKDSSHQVLQWKH'3VODYH"
Bus failure interrupt
(short-circuit,
connector unplugged)
Calls OB86 with the message 6WDWLRQIDLOXUH(incoming
event; diagnostic address of Slot 0 of the DP slave that is
assigned to the DP master)
with I/O access: Call of OB122 (I/O access error)
DP slave: RUN
STOP
Call of OB82 with the message 0RGXOHHUURU
(incoming event; diagnostic address of Slot 2 of the DP slave
that is assigned to the DP master; Variable
OB82_MDL_STOP=1)
DP slave: STOP
RUN
Call of OB82 with the message 0RGXOH2.
(outgoing event; diagnostic address of Slot 2 of the DP slave
that is assigned to the DP master; Variable
OB82_MDL_STOP=0)
(YDOXDWLRQLQWKHXVHUSURJUDP
The table below shows how you can, for example, evaluate RUN to STOP
transitions of the DP slave in the DP master.
Table 11-9 Evaluation in the DP master of RUN to STOP transitions by the DP slave
,QWKH'3PDVWHU ,QWKH'3VODYH&38['3
Diagnostic addresses: (Example)
Master diagnostic address =
Slave diagnostic address =
(Slot 0 of slave)
(Diagnostic) address for "Slot 2"=
(Slot 2 of slave)
Diagnostic addresses: (Example)
Slave diagnostic address =
Master diagnostic address = irrelevant
The CPU calls OB82 with the following
information:
OB82_MDL_ADDR:=
OB82_EV_CLASS:=B#16#39 (incoming
event)
OB82_MDL_DEFECT: = Module error
Tip: The CPU diagnostic buffer also contains
this information
In the user program you should also include
SFC 13 "DPNRM_DG" for reading out DP
slave diagnostic data.
CPU: RUN -> STOP
The CPU generates a DP slave
diagnostics message frame

Table of Contents

Other manuals for Siemens CPU 315-2 DP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CPU 315-2 DP and is the answer not in the manual?

Siemens CPU 315-2 DP Specifications

General IconGeneral
BrandSiemens
ModelCPU 315-2 DP
CategoryController
LanguageEnglish

Related product manuals