EasyManuals Logo
Home>Siemens>Relays>SIPROTEC 7RW80

Siemens SIPROTEC 7RW80 User Manual

Siemens SIPROTEC 7RW80
260 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #124 background imageLoading...
Page #124 background image
Functions
2.12 Auxiliary Functions
SIPROTEC, 7RW80, Manual
C53000-G1140-C233-1, Release date 10.2010
124
2.12.6.3 Information List
2.12.7 Energy Metering
The energy values are determinated via binary input pulses.
2.12.7.1 Setting Notes
Setting of parameter for meter resolution
Parameter 8315 MeterResolution can be used to maximize the resolution of the metered energy values by
Factor 10 or Factor 100 compared to the Standard setting.
2.12.7.2 Settings
2.12.7.3 Information List
No. Information Type of In-
formation
Comments
- OpHour> LV Operating hours greater than
272 SP. Op Hours> OUT Set Point Operating Hours
Addr. Parameter Setting Options Default Setting Comments
8315 MeterResolution Standard
Factor 10
Factor 100
Standard Meter resolution
No. Information Type of In-
formation
Comments
- Meter res IntSP_Ev Reset meter
888 Wp(puls) PMV Pulsed Energy Wp (active)
889 Wq(puls) PMV Pulsed Energy Wq (reactive)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7RW80 and is the answer not in the manual?

Siemens SIPROTEC 7RW80 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7RW80
CategoryRelays
LanguageEnglish

Related product manuals