EasyManuals Logo
Home>Thytronic>Security Sensors>SME2-IS

Thytronic SME2-IS User Manual

Thytronic SME2-IS
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #10 background imageLoading...
Page #10 background image
10
10
SME2-IS - Manual - 06 - 2021
GENERAL INFORMATION
2 GENERAL INFORMATION2 GENERAL INFORMATION
Preface
SME2-IS fault detectors are conforming with ENEL specication GSTP011 (Protection and control
device for MV substation – RGDM control unit); they are installed in remote controlled substations
to detect phase faults and ground faults on both isolated neutral grids and compensated neutral
grids, without the need for modication to handle switching between the two grid congurations and
independently of the power direction;
In particular:
• they detect multi-phase faults and single-phase ground faults,
• they detect line undervoltage,
• they measure the voltage and the active and reactive power of the MV line,
• the open and close the DY800 in response to faults or when remotely operated by UP,
• they interface with the generators on the MV grid to coordinate the regulation of the voltage along
the line and remote disconnection signals.
The input circuits are suited to acquire measurements with integrated phase current/voltage sen-
sors; the device is able, with SW selection, to acquire the current values from active sensors (signal
proportional to the current transduced by the sensor) or passive sensors (DJ 5400 and GSTC005 -
signal proportional to the value of the time derivative of the current), and can measure current and
voltage values with IEC 61869-10 and IEC 61869-11 low power sensors.
The homopolar values are calculated vectorially from the measured phase currents and voltages.
Voltage measurement inputs are available with capacitive voltage dividers.
Two Ethernet communications ports are available, of which one runs the IEC61850 protocol.
To ensure full compatibility with any RTUs already on the secondary systems, the SME2-IS device
is equipped with a dual interface to dialogue with both the UP (DX1215) and future communications
equipment.
The system can be calibrated, programmed and its logs and values read with a PC, or via the Ether-
net communications port using the freely available ThySetter software; all the above operations are
also available via the front panel keypad (MMI).
Picture
Main Characteristics
Metal enclosure
Backlit LCD display
Ten indicator LEDs on the front panel, freely programmable
RESET button for resetting the indicators
Switch open/close buttons
Hot Line Tag function button
Switch for enabling/disabling auto-reclose

Table of Contents

Other manuals for Thytronic SME2-IS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Thytronic SME2-IS and is the answer not in the manual?

Thytronic SME2-IS Specifications

General IconGeneral
BrandThytronic
ModelSME2-IS
CategorySecurity Sensors
LanguageEnglish