62
62
SME2-IS - Manual - 06 - 2021
MEASUREMENTS, LOGICAL STATES AND COUNTERS
Low level faults can be ignored or reported; this can be done by setting to ON or OFF the parameter
Report LOW LEVEL fault in the menu Set \ Fault relay.
The protection functions remain active even in case of low level faults:
Internal BUS low level OK/NOT OK
Check I/Os assigned to low level runtime protection OK/NOT OK
Check I/Os assigned to low level runtime PLC OK/NOT OK
Run-time DFR OK/NOT OK
All remaining (high level) faults, deactivate the protection functions:
Protection and automations IN SERVICE/OUT OF SERVICE
General diagnostics OK/NOT OK
Startup database OK/NOT OK
Run-time database OK/NOT OK
Startup DSP board OK/NOT OK
Run-time DSP board OK/NOT OK
Startup memory OK/NOT OK
Run-time memory OK/NOT OK
Startup serial ash OK/NOT OK
Run-time serial ash OK/NOT OK
Run-time SF memo OK/NOT OK
Run-time SF memo OK/NOT OK
Internal BUS high level OK/NOT OK
Internal BUS low level OK/NOT OK
Run-time DFR OK/NOT OK
Startup PLC status OK/NOT OK
Run-time PLC OK/NOT OK
Breaker fault OK/NOT OK
Capacitive divider voltage calibration OK/NOT OK
MMI module
Startup OK/NOT OK
run-time OK/NOT OK
The diagnostic information can be associated with an output relay selected with the parameter in
the menu Set \ Fault relay
[1]
Selective block - BLOCKS
Selective block status threshold I> ON/OFF
Selective block status threshold I>> ON/OFF
Selective block status threshold I>>> ON/OFF
Selective block status threshold I>>>> ON/OFF
Selective block status threshold IE> ON/OFF
Selective block status threshold IED> ON/OFF
Selective block status threshold IED>> ON/OFF
Selective block status threshold IED>>> ON/OFF
Selective block status threshold IED>>>> ON/OFF
Virtual inputs
Virtual input status VIN1 ON/OFF
Virtual input timeout VIN1 ON/OFF
Virtual input status VIN2 ON/OFF
Virtual input timeout VIN2 ON/OFF
Virtual input status VINx ON/OFF
Virtual input timeout VINx ON/OFF
......
Virtual input status VIN32 ON/OFF
Virtual input timeout VIN32 ON/OFF
Virtual outputs
Virtual output status VOUT1 ON/OFF
Virtual output timeout VOUT1 ON/OFF
Virtual output status VOUT2 ON/OFF
Virtual output timeout VOUT2 ON/OFF
Virtual output status VOUTx ON/OFF
Virtual output timeout VOUTx ON/OFF
......
Virtual output status VOUT32 ON/OFF
Virtual output timeout VOUT32 ON/OFF
Fault logging - SFR
Logging is activated by at least one of the following causes (up to eight at the same time):
Switching (OFF-ON) of an output relay associated with the tripping of a control or protection
function
Note 1 A relay may only be assigned to the self-diagnostics function by a level 1 user

Table of Contents

Other manuals for Thytronic SME2-IS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Thytronic SME2-IS and is the answer not in the manual?

Thytronic SME2-IS Specifications

General IconGeneral
BrandThytronic
ModelSME2-IS
CategorySecurity Sensors
LanguageEnglish