SME2-IS - Manual - 06 - 2021
TECHNICAL CHARACTERISTICS
Threshold I>>>>
Directionality (I>>>> Dir) Directional, Non directional
Reset delay (t>>>>
RES
)
0.00...100.0 s
Second harmonic restraint (I>>>>
2ndh-REST
)
ON/OFF
Time-independent
Fourth time-independent threshold (I>>>>
def
) 0.02...3.00 I
n
Characteristic angle (ThetaP>>>>
def
) 0...359 °
Tripping time (t>>>>
def
) 0.05...10.00 s
Tripping sector (Beta I >>>>) 0...90 °
Residual overcurrent - 50N/51N
Threshold IE>
Reset delay (t
E
>
RES
) 0.00...100.0 s
Second harmonic restraint (I
E
>
2ndh-REST
)
ON/OFF
Time-independent
First time-independent threshold (
I
E
>
def
) 0.010...2,000 I
En
Tripping time (t
E
>
def
) 0.05...30.0 s
Threshold IE>>
Reset delay (t
E
>>
RES
) 0.00...100.0 s
Second harmonic restraint (I
E
>>
2ndh-REST
)
ON/OFF
Time-independent
Second time-independent threshold (
I
E
>>
def
) 0.010...2.000 I
En
Tripping time (t
E
>>
def
) 0.05...10.00 s
Ground directional overcurrent - 67N
Threshold I
ED
>
Reset delay (t
ED
>
RES
) 0.00...100.0 s
Time-independent
First time-independent threshold (I
ED
>
def
- U
ED
>
def
)
Residual current tripping time 0.002...0.032 I
n
Residual voltage tripping value 0.010...1.000 U
En
Characteristic angle 0...359°
Tripping half-sector 1...180°
Tripping time (t
ED
>
def
) 0.05...30.0 s
Threshold I
ED
>>
Reset delay (t
ED
>>
RES
) 0.00...100.0 s
Time-independent
Second time-independent threshold (I
ED
>>
def
- U
ED
>>
def
)
Residual current tripping time 0.002...0.032 I
n
Residual voltage tripping value 0.010...1.000 U
En
Characteristic angle 0...359°
Tripping half-sector 1...180°
Tripping time (t
ED
>>
def
) 0.05...15.0 s
Threshold I
ED
>>>
Reset delay (t
ED
>>>
RES
) 0.00...100.0 s
Time-independent
Third time-independent threshold (I
ED
>>>
def
- U
ED
>>>
def
)
Residual current tripping time 0.002...1.000 I
n
Residual voltage tripping value 0.010...1.000 U
En
Characteristic angle 0...359°
Tripping half-sector 1...180°
Tripping time (t
ED>
>>
def
) 0.05...1.00 s
Threshold I
ED
>>>>
Reset delay (t
ED
>>>
RES
) 0.00...100.0 s
Time-independent
Tripping time (t
ED
>>>>
def
) 0.50...2.00 s
ALB frequency (automatic load balancer)
Block thresholds
Minimum voltage Ueac<def 0.05 ...1.40 En ( step 0.05 En)
Tripping time tUeac< 0.05 ...9.99 s (step 0.01 s)
10.0 .. 99.9 s (step 0.1 s)
100 ...1000 s (step 1 s)
Maximum voltage Ueac>def 0.05 ...1.40 En ( step 0.05 En)
Tripping time tUeac> 0.05 ...9.99 s (step 0.01 s)
10.0 .. 99.9 s (step 0.1 s)
100 ...1000 s (step 1 s)
Maximum unbalance ULS>def 0.05 ...1.00 Um ( step 0.05 Um)
Reset delay tULS>RES 0.00 ...9.99 s (step 0.01 s)
10.0 .. 100.0 s (step 0.1 s)
Tripping time tULS> 0.05 ...9.99 s (step 0.01 s)
10.0 .. 99.9 s (step 0.1 s)

Table of Contents

Other manuals for Thytronic SME2-IS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Thytronic SME2-IS and is the answer not in the manual?

Thytronic SME2-IS Specifications

General IconGeneral
BrandThytronic
ModelSME2-IS
CategorySecurity Sensors
LanguageEnglish