5 - 16 RTHC-IOM-1C
Start Reset Setpoint
The start reset range is 4 to 30
°
F (2.2 to 16.7
°
C) for
return reset with the ROM default of 10
°
F (5.6
°
C).
For outdoor reset, the range is 50 to 130
°
F (10 to
54.4
°
C) for with the ROM default of 90
°
F (32.2
°
C).
Max Reset Setpoint
The maximum reset range is 0 to 20
°
F (0.0 to
11.1
°
C) for return reset with the ROM default of 5
°
F
(2.8
°
C). For outdoor reset, the range is 0 to 20
°
F (0.0
to 11.1
°
C) for with the ROM default of 5
°
F (2.8
°
C).
Ice Building Enable
This data will be displayed only if the ice making
option is installed.
where disable is the ROM default.
Front Panel Ice Termination Setpoint
This data will be displayed only if the ice-making
option is installed.
NOTE: When the chiller is in the “ice building” mode,
it will run at full load to make ice until the return water
(glycol) drops below the above setpoint.
The range of values is 20.0 to 32.0
°
F (-6.7 to 0.0
°
C)
in increments of 1 or 0.1
°
F or C, depending on the
service setup screen. The ROM default is 27.0
°
F
(-2.8
°
C).
Ice Making To Normal Cooling Transition Timer
This data will be displayed only if the ice making
option is installed.
The range of values is 0 to 10 minutes. The ROM
default is 5 minutes.
Chilled Water Setpoint Source
This screen will only be displayed if the external
chilled water setpoint is installed at the machine
configuration menu. If the Tracer option is installed,
the word “Default” will appear in front of the setpoint
source.
Possible values of [source] are Front Panel (ROM
default) and External source.
Current Limit Setpoint Source
This screen will only be displayed if the external
chilled water setpoint is installed in the machine
configuration menu. If the Tracer option is installed,
the word “Default” will appear in front of the setpoint
source.
where [source] is Front Panel (ROM default) or
External.
Setpoint Source Override
Possible values of [source] are none (ROM default),
“Use Front Panel setpoints,” and “Override Tracer.
Use default setpoints” for which the Tracer option
must be installed. this is a global override that will
[type] Start Reset: xxx.x F
Press (+) (-) to Change Setting
[type] Max Reset Setpoint: xxx.x F
Press (+) (-) to Change Setting
Ice Building [d/e]
Press (+) (-) to Change Setting
Panel Ice Termination Setpoint: xxx.x F
Press (+) (-) to Change Setting
Ice-To-Normal Cooling Timer: xx min
Press (+) (-) to Change Setting
[Default] Chilled Water Setpoint Source:
[source]
[Default] Current Limit Setpoint Source:
[source]
Setpoint Source Override
[source]