Installation, Operation and Maintenance 2 - 5
*Designator corresponds to digits 6, 7, 12, 13, 16, 17 of model
number
Lifting Procedure
CAUTION
CAUTION: Unit Moving!
Never use a forklift to move the unit.
The skid is not designed to support
the unit at any one point and using a
forklift to move the equipment may
cause unit damage.
NOTE: If absolutely necessary, the chiller can be
pushed or pulled across a smooth surface if it is
bolted to wood shipping mounts.
WARNING
Do not remove the wood mounts
until the unit is in its final location.
Removal of wood shipping mounts
prior to unit final locating could
result in injury or death and equip-
ment damage.
1 When the unit is at its final location, remove the
shipping bolts that secure the unit to the wood
base mounts.
2 Rig the unit properly and lift from above or jack
the unit (alternate moving method). Use the points
shown on the rigging diagram that ships with the
unit as shown in
Figure 6
. Remove the base
mounts.
Table 8
Unit Weights (lb (kg)) (see Figure 5 )
Location (Point)
Unit Designator
(corresponds to digits 6, 7, 12, 13, 16, 17 of unit model number)
D3D2E2 D3F2F3 D3G3G3 E3D2E2 E3F2F3 E3G3G3
A 3841 (1742) 4870 (2209) 5445 (2470) 3906 (1772) 4940 (2241) 5489 (2490)
B 2880 (1306) 3670 (1665) 4559 (2068) 2919 (1324) 3715 (1685) 4588 (2081)
C 3343 (1516) 3833 (1739) 4431 (2010) 3397 (1541) 3886 (1763) 4505 (2043)
D 4832 (2192) 4931 (2237) 5535 (2511) 4924 (2234) 5013 (2274) 5638 (2557)
Unit Wt (without
water)
14896
(6757)
17304
(7849)
19970
(9058)
15146
(6870)
17554
(7962)
20220
(9172)
Est. Water Wt
1004 (455) 1396 (633) 2130 (966) 1004 (455) 1396 (633) 2130 (966)
Total Installed Wt
15900
(7189)
18700
(8482)
22100
(10024)
16150
(7325)
18950
(8596)
22350
(10138)
Table 9
Center of Gravity (in) (see Figure 5 )
*Unit Configuration X Y Z
E3G3G3 30.80 63.81 37.62
E3F2F3 27.64 63.46 38.33
E3D2E2 25.90 60.05 40.50
D2G3G3 30.85 63.48 37.44
D2F2F3 27.70 63.40 38.14
D2D2E2 25.97 59.95 40.31
D1G2G2 30.77 63.55 37.72
D1F1F2 27.92 63.47 38.70
D1D1E1 25.91 60.00 40.47
C2G1G1 30.58 63.46 38.15
C2D3E3 26.13 59.74 40.08
C2B3C2 24.81 59.96 40.52
C1E1F1 26.36 63.49 40.95
C1B3C2 24.81 59.96 40.52
C1B2C1 24.71 60.01 40.78
B2C2D2 22.40 58,29 33.51
B2B2B2 22.88 58.11 35.43
B1C1D1 22.32 58,23 33.65
B1B1B1 22.84 58.13 35.59