BlueCool S Series 10 Overview of Programming Functions
39
10.3.4 Setting level 3
Parameter u: Temperature unit
Setting range: 00, 01
Factory setting: 00
Changing over the temperature display from °C to °F for all
temperature values
00 = °C
01 = °F
Parameter 0: Switch-off temperature, compressor
cooling (minimum)
Setting range: -4 to 15 °C
24 to 59 °F
Factory setting: -2 °C
28 °F
This parameter is used to set the minimum evaporator
temperature. If this temperature value is dropped below
during normal operation, then the compressor is switched
off immediately.
Parameter 1: Switch-off temperature, compressor
cooling
Setting range: -4 to 15 °C
24 to 59 °F
Factory setting: 0 °C
32 °F
This parameter is use to set the lower evaporator
temperature. If this temperature value is dropped below
during normal operation for the time set in Parameter 7,
then the compressor is switched off.
Parameter 2: Switch-on temperature, compressor
cooling
Setting range: 2 to 18 °C
35 to 65 °F
Factory setting: 4 °C
39 °F
This parameter is used to set the evaporator temperature at
which the compressor is to be switched on again. If this
temperature value is exceeded during normal operation,
and if the room temperature also has a corresponding value,
then the compressor is switched on.
Parameter 3: Switch-off temperature, compressor
heating
Setting range: 30 to 55 °C
86 to 131 °F
Factory setting: 52 °C
126 °F
This parameter is used to set the maximum condenser
temperature at which the compressor is switched off.
Parameter 4: Switch-on temperature, compressor
heating
Setting range: 27 to 50 °C
81 to 122 °F
Factory setting: 48 °C
118 °F
This parameter is used to set the condenser temperature at
which the compressor is to be switched on again. If this
temperature value is dropped below during normal
operation, and if the room temperature also has a
corresponding value, then the compressor is switched on.
ATTENTION
Changing this value can result in impairment of
operation and damage to the air-conditioning
system.
ATTENTION
Changing this value can result in impairment of
operation and damage to the air-conditioning
system.
ATTENTION
Changing this value can result in impairment of
operation and damage to the air-conditioning
system.
ATTENTION
Changing this value can result in impairment of
operation and damage to the air-conditioning
system.
ATTENTION
Changing this value can result in impairment of
operation and damage to the air-conditioning
system.