5-7-5-2. External speed limit
Limit the speed output of torque control mode by the analog voltage command input from V-REF
terminal.
V-REF function
distribution
Make V-REF as external
speed limit input, actual
speed limit depends on
external analog speed limit
1. The analog voltage has no polarity. The absolute value of the voltage is suitable for forward and
reverse direction.
2. The parameter value is related to voltage command and P3-01 when it is used as speed limit value.
For example: P3-01=5000 (voltage of rated speed is 5.0V), V-REF voltage command is 1.0V, the
speed limit is 20% of rated speed.
5-7-5-3. Speed up to limit value output
Range: 0000-0013. Distribute to output terminal through P5-43. When it set to 0001, it means
output from SO1.
5-8.Torque control (internal setting)
Torque command filter time
Internal forward speed limit of torque control
Internal reverse speed limit of torque control
V-REF function distribution
Speed up to limit value output
/SPD-D
direction
selection
internal forward speed limit in torque control mode
Note: the actual speed is max speed even this parameter speed is larger than the max speed.
internal reverse speed limit in torque control mode
Note: the actual speed is max speed even this parameter speed is larger than the max speed.