Parameter Value
Lamp load (max.) 5 W
Max. leakage current with signal 0 0.5 mA
Output type Non-protected
Protection type External fuse on each channel
Rated protection fuse (for each channel) 3 A fast
Demagnetization when inductive loads are
switched off
Must be performed externally according to driven
load specification
Switching Frequencies
With inductive loads Max. 0.5 Hz
With lamp loads Max. 11 Hz at max. 5 W
Short-circuit-proof / Overload-proof No
Overload message No
Output current limitation No
Resistance to feedback against 24 V
DC
No
Connection of 2 outputs in parallel Not possible
Max. cable length
Shielded 500 m
Unshielded 150 m
6.2.2.9 Ordering data
Part no. Description Product life cycle phase *)
1SAP 187 000 R0002 TA5105-4DOT: AC500, digital output
module option board, 4DO-T 24 VDC /
0.5 A, spring/cable front terminal 3.50
mm pitch
Active
Spare parts
1SAP 187 400 R0014
**)
TA5220-SPF7: spring terminal block,
removable, 7-pin, spring front, cable
front, 6 pieces per packing unit
Active
*) Modules in lifecycle Classic are available from stock but not recommended
for planning and commissioning of new installations.
**) The needed spring terminal block is always delivered with the option board.
The terminal block listed in the table is for spare part only if needed.
Option boards > TA5105-4DOT - Digital output module option board
2021/06/293ADR010635, 2, en_US116