Electromagnetic Compatibility
Immunity against transient interference vol-
tages (burst):
According to IEC 61000-4-4, zone B, crite-
rion B
Supply voltage units (DC) 2 kV
Digital inputs/outputs (24 VDC) 1 kV
Digital inputs/outputs (120 VAC...240 VAC) Relay 2 kV
Ethernet 1 kV
Immunity against the influence of line-con-
ducted interferences (CW conducted):
According to IEC 61000-4-6, zone B, crite-
rion A
Test voltage 20 V pass A
High energy surges According to IEC 61000-4-5, zone B, crite-
rion B
Power supply DC
1 kV CM / 0.5 kV DM
1
)
DC I/O supply
1 kV CM / 0.5 kV DM
1
)
Buses, shielded ETH
AC I/O unshielded
2
) 1 kV DM
1
)
I/O analog, I/O DC unshielded
2
) 1 kV CM
1
)
Radiation (radio disturbance) According to IEC 55011, group 1, class A
1
) CM = Common Mode, DM = Differential Mode
2
) When DC I/O inputs are used with AC voltage, external filters limiting high energy surges to 1
kV CM / 0.5 DM are required to meet requirements according IEC 61131-2.
6.4.6 Mechanical data
Parameter Value
Mounting Horizontal
Degree of protection IP 20 (if all terminal screws are tightened)
Housing Classification V0 according to UL 94
Vibration resistance acc. to EN 61131-2 all three axes (DIN rail mounting)
5 Hz...8.4 Hz, continuous 3.5 mm
8.4 Hz...150 Hz, continuous 1 g
Shock test All three axes
15 g, 11 ms, half-sinusoidal
Mounting of the modules:
DIN rail according to DIN EN 50022 35 mm, depth 7.5 mm or 15 mm
Mounting with screws Screws with a diameter of 4 mm
Fastening torque 1.2 Nm
6.4.7 Approvals and certifications
Information on approvals and certificates can be found in the corresponding chapter of the
Main catalog, PLC Automation.
System data AC500-eCo V3 > Approvals and certifications
2021/06/293ADR010635, 2, en_US156