See also the following chapter:
8.3.4.2 Function block
If the counter value reaches the “LowerLimitOn” preset, it will write to the LimitSwitch output
based on the signal until the “UpperLimitOn” preset is reached.
8.3.5 Use the onboard I/Os as PTO (pulse-train output) with 100 kHz frequency (max. 2
PTO using PTO HW channels)
8.3.5.1 Parameter configuration
The user can configure the following output channels as PTO (pulse-train output).
“PTO”: Output channel 4
“PTO”: Output channel 5
“PTO”: Output channel 6
“PTO”: Output channel 7
If the user configures the output 4 as PTO, the output 5 is automatically configured as PTO.
If the user configures the output 6 as PTO, the output 7 is automatically configured as PTO.
Simple motion
System technology > Use the onboard I/Os as PTO (pulse-train output) with 100 kHz frequency (max. 2 PTO using PTO HW channels)
2021/06/29 3ADR010635, 2, en_US 181