Part no. Description
1SAP 187 400 R0014 TA5220-SPF7: spring terminal block, removable, 7-pin, spring front,
cable front, 6 pieces per packing unit
1SAP 187 400 R0015 TA5220-SPF8: spring terminal block, removable, 8-pin, spring front,
cable front, 6 pieces per packing unit
6.4 System data AC500-eCo V3
6.4.1 Environmental conditions
Table 31: Process and supply voltage
Parameter Value
Voltage 24 V (-15 %, +20 %)
Protection against reverse polarity Yes
Allowed interruptions of power supply, according to EN 61131-2
DC supply Interruption < 10 ms, time between 2 interruptions >
1 s, PS2
NOTICE!
Exceeding the maximum power supply voltage (> 30 VDC) for process or
supply voltages could lead to unrecoverable damage of the system. The system
could be destroyed.
Parameter Value
PM5012 PM5032 PM5052 PM5072
Temperature
Operating
Horizontal mounting
Standard temperature
range
0 °C...+55 °C 0 °C...+60 °C
Wide temperature
range
- -20 °C...+70 °C
Vertical mounting (output load reduced to 50 % per group)
Standard temperature
range
0 °C...+40 °C
Wide temperature
range
- -20 °C...+40 °C
Storage -40 °C...+70 °C
Transport -40 °C...+70 °C
Humidity Max. 95 %, without condensation
Air pressure
Operating > 800 hPa / < 2000 m
Storage > 660 hPa / < 3500 m
Device specifications
System data AC500-eCo V3 > Environmental conditions
2021/06/293ADR010635, 2, en_US154