6.2 CS1 CONTROL SIGNALS
Loading CS1 connects the 53MC5000 Controller function blocks for operation as a standard Single
Loop Controller. As shown in Figure 6-1, up to ten control signals are available; however, only two
are essential for operation: they are AI0 - Process Variable, and AO0 - Control Output. If the other
eight signals are not required, then their respective datapoints should be left at the default values.
Table 6-1 below describes the ten signals in CS1.
Table 6-1. CS1 Control Signals
Control
Signal Definition
Cord
Set
ITB
Rear
Term
Board
Signal
AI0 - Process
Variable Input
This analog input signal represents the value
of the process to be manipulated by the
controller. It is compared to the control
setpoint to determine the Control Output value.
TB1-1 (+)
TB1-2 (-)
TB1-3
1 (+)
2 (-)
3
+24 V
AI0
SC
AI1 - Remote
Setpoint Input
This analog input signal represents the value
to be used as the control setpoint when remote
setpoint operation is selected with the
faceplate push buttons and enabled by DI1.
TB1-5 (+)
TB1-6 (-)
TB1-7
4 (+)
5 (-)
6
+24 V
AI1
SC
AI2 - Additive
Feed Forward
Input
This analog input signal value is added to the
PID result to make up the Control Output value
when Auto operation is active.
TB1-9
TB1-10 (+)
TB1-11 (-)
1
7 (+)
8 (-)
+24 V
AI2
SC
AI3 - Tracking
Input
This analog input signal value becomes the
Control Output value when the Force Output
Tracking contact input is open and datapoint
L119 (Enable Output Tracking) is configured to
a 1.
TB1-13
TB1-14 (+)
TB1-15 (-)
4
9 (+)
8 (-)
+24 V
AI3
SC
AO0 - Control
Output
This is the 4-20 mA output signal that drives
the final control element.
TB1-17 (+)
TB1-18 (-)
10 (+)
11 (-)
AO0
PC
AO1 -
Retransmitted
PV
This output signal reflects the Process Variable
Input signal value over a 4-20 mA range.
TB1-19 (+)
TB1-20 (-)
12 (+)
11 (-)
AN01
PC
DI0 - Force
Output
Tracking
When an open contact is present on this input,
the Control Output value is forced to match the
Tracking Input value when datapoint L119
(Enable Output Tracking) is configured to a 1.
TB2-1 (+)
TB2-2 (-)
13 (+)
14 (-)
DI0
PC
DI1 - Remote
Setpoint
Enable
When a closed contact is present on this input,
the operator can select the setpoint value to be
set by the value of the Remote Setpoint Input
with the R/L push button.
TB2-3 (+)
TB2-4 (-)
15 (+)
14 (-)
DI1
PC
DO0 - Process
Alarm 1
This contact is closed when the Process
Variable value is not within the C103 value
setting (Alarm Limit 1 datapoint); otherwise, the
contact is open.
TB2-5 (+)
TB2-6 (-)
16 (+)
17 (-)
DO0
PC
DO1 - Process
Alarm 2
This contact is closed when the Process
Variable value is not within the C104 value
setting (Alarm Limit 2 datapoint); otherwise, the
contact is open.
TB2-7 (+)
TB2-8 (-)
18 (+)
17 (-)
DO1
PC
53MC5000 Process Control Station