Table 1-5. OPTO 22 Module Specifications for 16DI/DO ITB
Safety classification: FM Approved: Nonincendive for Class 1, Div. 2, Group A, B, C, & D
hazardous locations as part of the 16DI/DO ITB.
WARNING
It is the user’s responsibility to install all associated switches and load
apparatus in accordance with ANSI/NFPA 70, National Electrical Code.
Rules and requirements for the installation and wiring of equipment in
Class 1, Division 2 Hazardous (Classified) Locations are found in
Article 501 of the Code.
CSA Certified.
Meets IEEE surge withstand specification.
UL recognized.
4000 V ac optical isolation.
Will withstand one cycle surge of 80 Amperes.
Built-in LED Status Indicator.
Output modules have replaceable fuses.
OPTO 22 AC Input Modules
OPTO 22
Part Number
16DI/DO
Voltage Input Voltage Range
Input
Current @
Max V In
Input
Maximum
for No Output
G41DC5 5 V dc 12 - 32 V ac 25 mA 3 V ac
G41DC5G 5 V dc 35 - 60 V ac 25 mA 9 V ac
G41AC5 5 V dc 90 - 140 V ac 11 mA 45 V ac
G41AC5A 5 V dc 180 - 280 V ac 6.5 mA 80 V ac
G41DC24 24 V dc 12 - 32 V ac 25 mA 3 V ac
G41AC24 24 V dc 90 - 140 V ac 11 mA 45 V ac
OPTO 22 AC Output Modules
OPTO 22
Part Number
16DI/DO
Voltage
Output Line
Voltage
Range
Load
Current
@ 45
°
C
Load
Current
@ 70
°
C
Maximum
Off State
Leakage
G40AC5 5 V dc 12 - 140 V ac 3 Amps 2 Amps 5 mA ac
G40AC5A 5 V dc 24 - 280 V ac 3 Amps 2 Amps 2.5 mA ac
G40AC5A5(NC) 5 V dc 24 - 280 V ac 3 Amps 2 Amps 2.5 mA ac
G40AC24 24 V dc 12 - 140 V ac 3 Amps 2 Amps 5 mA ac
G40AC24A 24 V dc 24 - 280 V ac 3 Amps 2 Amps 2.5 mA ac
OPTO 22 DC Input Modules
OPTO 22
Part Number
16DI/DO
Voltage Input Voltage Range
Input
Current @
Max V In
Input
Maximum
for No Output
G41C5 5 V dc 10 - 32 V dc 25 mA 3 V dc
G41DC5B 5 V dc 4 - 16 V dc 45 mA 1 V dc
G41DC5D 5 V dc 2.5 - 28 V dc 30 mA 1 V dc
1 of 2
53MC5000 Process Control Station
1-16