U1<
ST1
TR1
tReset1
t1
IEC10000040-3-en.vsd
IEC10000040 V3 EN-US
Figure 132: Example for Definite Time Delay stage1 operation
8.1.7.3 Blocking
M15326-20 v8
It is possible to block Two step undervoltage protection UV2PTUV partially or
completely, by binary input signals or by parameter settings, where:
BLOCK:
blocks all outputs
BLKTR1: blocks all trip outputs of step 1
BLKST1: blocks all start and trip outputs related to step 1
BLKTR2: blocks all trip outputs of step 2
BLKST2: blocks all start and trip outputs related to step 2
If the measured voltage level decreases below the setting of IntBlkStVal1, either the
trip output of step 1, or both the trip and the START outputs of step 1, are blocked.
The characteristic of the blocking is set by the IntBlkSel1 parameter. This internal
blocking can also be set to Off resulting in no voltage based blocking.
Corresponding settings and functionality are valid also for step 2.
In case of disconnection of the high voltage component the measured voltage will
get very low. The event will START both the under voltage function and the
blocking function, as seen in figure
133. The delay of the blocking function must
be set less than the time delay of under voltage function.
Section 8 1MRK 506 382-UEN A
Voltage protection
270 Line distance protection REL650 2.2 IEC
Technical manual

Table of Contents

Other manuals for ABB REL650

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REL650 and is the answer not in the manual?

ABB REL650 Specifications

General IconGeneral
BrandABB
ModelREL650
CategoryProtection Device
LanguageEnglish

Related product manuals